Uninterruptible Power Supply (UPS) Management Protocol -- Commands and Responses
draft-rprice-ups-management-protocol-02

The information below is for an old version of the document.
Document Type
This is an older version of an Internet-Draft that was ultimately published as RFC 9271.
Author Roger Price
Last updated 2021-03-06 (Latest revision 2021-02-18)
RFC stream (None)
Formats
IETF conflict review conflict-review-rprice-ups-management-protocol, conflict-review-rprice-ups-management-protocol, conflict-review-rprice-ups-management-protocol, conflict-review-rprice-ups-management-protocol, conflict-review-rprice-ups-management-protocol, conflict-review-rprice-ups-management-protocol
Stream Stream state (No stream defined)
Consensus boilerplate Unknown
RFC Editor Note (None)
IESG IESG state Became RFC 9271 (Informational)
Telechat date (None)
Responsible AD (None)
Send notices to (None)
draft-rprice-ups-management-protocol-02
IETF                                                       R. Price, Ed.
Internet-Draft                                 Network UPS Tools Project
Intended status: Informational                              6 March 2021
Expires: 7 September 2021

 Uninterruptible Power Supply (UPS) Management Protocol -- Commands and
                               Responses
                draft-rprice-ups-management-protocol-02

Abstract

   This text describes the command/response protocol currently used in
   the management of Uninterruptible Power Supply (UPS) units and other
   power devices often deployed in small offices, and in IT
   installations subject to an erratic public power supply.  The UPS
   units typically interface to an Attachment Daemon in the system they
   protect.  This daemon is in turn polled by a Management Daemon which
   notifies users and system administrators of power supply incidents,
   and takes system shutdown decisions.  The commands and responses
   described by this text are exchanged between the UPS Attachment
   Daemon and the Management Daemon.  Current practice leads to weak
   security and this is addressed in the Security and IANA
   Considerations.

Status of This Memo

   This Internet-Draft is submitted in full conformance with the
   provisions of BCP 78 and BCP 79.

   Internet-Drafts are working documents of the Internet Engineering
   Task Force (IETF).  Note that other groups may also distribute
   working documents as Internet-Drafts.  The list of current Internet-
   Drafts is at https://datatracker.ietf.org/drafts/current/.

   Internet-Drafts are draft documents valid for a maximum of six months
   and may be updated, replaced, or obsoleted by other documents at any
   time.  It is inappropriate to use Internet-Drafts as reference
   material or to cite them other than as "work in progress."

   This Internet-Draft will expire on 7 September 2021.

Copyright Notice

   Copyright (c) 2021 IETF Trust and the persons identified as the
   document authors.  All rights reserved.

Price                   Expires 7 September 2021                [Page 1]
Internet-Draft           UPS management protocol              March 2021

   This document is subject to BCP 78 and the IETF Trust's Legal
   Provisions Relating to IETF Documents (https://trustee.ietf.org/
   license-info) in effect on the date of publication of this document.
   Please review these documents carefully, as they describe your rights
   and restrictions with respect to this document.  Code Components
   extracted from this document must include Simplified BSD License text
   as described in Section 4.e of the Trust Legal Provisions and are
   provided without warranty as described in the Simplified BSD License.

Table of Contents

   1.  Introduction  . . . . . . . . . . . . . . . . . . . . . . . .   3
     1.1.  How to read this text . . . . . . . . . . . . . . . . . .   4
     1.2.  Current practice  . . . . . . . . . . . . . . . . . . . .   4
     1.3.  Requirements Language . . . . . . . . . . . . . . . . . .   4
     1.4.  Comments  . . . . . . . . . . . . . . . . . . . . . . . .   4
   2.  Terminology . . . . . . . . . . . . . . . . . . . . . . . . .   5
     2.1.  Attachment Daemon . . . . . . . . . . . . . . . . . . . .   5
     2.2.  Driver  . . . . . . . . . . . . . . . . . . . . . . . . .   5
     2.3.  Event . . . . . . . . . . . . . . . . . . . . . . . . . .   5
     2.4.  Instant Command . . . . . . . . . . . . . . . . . . . . .   5
     2.5.  Management Daemon . . . . . . . . . . . . . . . . . . . .   5
     2.6.  NUT (Network UPS Tools) Project . . . . . . . . . . . . .   6
     2.7.  Primary . . . . . . . . . . . . . . . . . . . . . . . . .   6
     2.8.  Secondary . . . . . . . . . . . . . . . . . . . . . . . .   6
     2.9.  Session . . . . . . . . . . . . . . . . . . . . . . . . .   6
     2.10. UPS status  . . . . . . . . . . . . . . . . . . . . . . .   7
     2.11. UPS variable  . . . . . . . . . . . . . . . . . . . . . .   7
   3.  Protocol overview . . . . . . . . . . . . . . . . . . . . . .   7
   4.  Protocol specification  . . . . . . . . . . . . . . . . . . .   9
     4.1.  Notation used in this specification . . . . . . . . . . .   9
     4.2.  Commands  . . . . . . . . . . . . . . . . . . . . . . . .  10
       4.2.1.  "FSD" . . . . . . . . . . . . . . . . . . . . . . . .  10
       4.2.2.  "GET" . . . . . . . . . . . . . . . . . . . . . . . .  10
         4.2.2.1.  "CMDDESC" . . . . . . . . . . . . . . . . . . . .  10
         4.2.2.2.  "DESC"  . . . . . . . . . . . . . . . . . . . . .  11
         4.2.2.3.  "NUMLOGINS" . . . . . . . . . . . . . . . . . . .  11
         4.2.2.4.  "TYPE"  . . . . . . . . . . . . . . . . . . . . .  11
         4.2.2.5.  "UPSDESC" . . . . . . . . . . . . . . . . . . . .  12
         4.2.2.6.  "VAR" . . . . . . . . . . . . . . . . . . . . . .  13
       4.2.3.  "HELP"  . . . . . . . . . . . . . . . . . . . . . . .  13
       4.2.4.  "INSTCMD" . . . . . . . . . . . . . . . . . . . . . .  13
       4.2.5.  "LIST"  . . . . . . . . . . . . . . . . . . . . . . .  13
         4.2.5.1.  "CLIENT"  . . . . . . . . . . . . . . . . . . . .  14
         4.2.5.2.  "CMD" . . . . . . . . . . . . . . . . . . . . . .  14
         4.2.5.3.  "ENUM"  . . . . . . . . . . . . . . . . . . . . .  15
         4.2.5.4.  "RANGE" . . . . . . . . . . . . . . . . . . . . .  15
         4.2.5.5.  "RW"  . . . . . . . . . . . . . . . . . . . . . .  16

Price                   Expires 7 September 2021                [Page 2]
Internet-Draft           UPS management protocol              March 2021

         4.2.5.6.  "UPS" . . . . . . . . . . . . . . . . . . . . . .  16
         4.2.5.7.  "VAR" . . . . . . . . . . . . . . . . . . . . . .  17
       4.2.6.  "LOGIN" . . . . . . . . . . . . . . . . . . . . . . .  17
       4.2.7.  "LOGOUT"  . . . . . . . . . . . . . . . . . . . . . .  18
       4.2.8.  "PASSWORD"  . . . . . . . . . . . . . . . . . . . . .  18
       4.2.9.  "PRIMARY" . . . . . . . . . . . . . . . . . . . . . .  18
       4.2.10. "PROTVER" . . . . . . . . . . . . . . . . . . . . . .  18
       4.2.11. "SET" . . . . . . . . . . . . . . . . . . . . . . . .  19
       4.2.12. "STARTTLS"  . . . . . . . . . . . . . . . . . . . . .  19
       4.2.13. "USERNAME"  . . . . . . . . . . . . . . . . . . . . .  19
       4.2.14. "VER" . . . . . . . . . . . . . . . . . . . . . . . .  20
     4.3.  Error responses . . . . . . . . . . . . . . . . . . . . .  20
   5.  Statuses and Events . . . . . . . . . . . . . . . . . . . . .  23
     5.1.  Status symbols  . . . . . . . . . . . . . . . . . . . . .  23
     5.2.  Events  . . . . . . . . . . . . . . . . . . . . . . . . .  26
   6.  IANA Considerations . . . . . . . . . . . . . . . . . . . . .  27
     6.1.  Namespaces used by Command, Responses, Statuses and
           Variables . . . . . . . . . . . . . . . . . . . . . . . .  28
     6.2.  Port name and number used to manage UPS units . . . . . .  28
       6.2.1.  Current situation . . . . . . . . . . . . . . . . . .  28
         6.2.1.1.  Port nut/3493 . . . . . . . . . . . . . . . . . .  28
         6.2.1.2.  Port ups/401  . . . . . . . . . . . . . . . . . .  28
       6.2.2.  Request to IANA . . . . . . . . . . . . . . . . . . .  29
   7.  Security Considerations . . . . . . . . . . . . . . . . . . .  29
     7.1.  Agent verification  . . . . . . . . . . . . . . . . . . .  29
     7.2.  Encryption  . . . . . . . . . . . . . . . . . . . . . . .  30
     7.3.  Current security practice . . . . . . . . . . . . . . . .  30
     7.4.  Security needs  . . . . . . . . . . . . . . . . . . . . .  31
       7.4.1.  Attachment Daemon shim  . . . . . . . . . . . . . . .  31
       7.4.2.  Management Daemon shim  . . . . . . . . . . . . . . .  31
   8.  Acknowledgments . . . . . . . . . . . . . . . . . . . . . . .  32
   9.  Normative References  . . . . . . . . . . . . . . . . . . . .  32
   10. Informative References  . . . . . . . . . . . . . . . . . . .  32
   Appendix A.  Variables and Instant Commands . . . . . . . . . . .  33
     A.1.  UPS variables . . . . . . . . . . . . . . . . . . . . . .  33
     A.2.  UPS readable and writable variables . . . . . . . . . . .  37
     A.3.  UPS Instant Commands  . . . . . . . . . . . . . . . . . .  39
   Appendix B.  Change Log . . . . . . . . . . . . . . . . . . . . .  39
     B.1.  Changes in version 01 . . . . . . . . . . . . . . . . . .  39
     B.2.  Changes in version 02 . . . . . . . . . . . . . . . . . .  40
   Author's Address  . . . . . . . . . . . . . . . . . . . . . . . .  40

1.  Introduction

Price                   Expires 7 September 2021                [Page 3]
Internet-Draft           UPS management protocol              March 2021

1.1.  How to read this text

   The editor recommends that you read the HTML version of this text.
   It renders the protocol symbols such as "OL" correctly without
   quotation marks.

   To lighten the text, the term "UPS" is used when "Managed Power
   Device" would be more complete.  The reader should understand the
   simple "UPS" to include other managed power devices.

      |  
      |  // Ed: To be removed.  The Idnits tool signals false positives
      |  when
      |  // reading variable names such as "ups.delay.shutdown".  It
      |  wrongly
      |  // assumes that they are domain names and applies RFC2606 which
      |  calls
      |  // for use of domain names such as "example.com"

1.2.  Current practice

   This text documents UPS management techniques and current UPS
   management practice published by the NUT Project (2.6) which has been
   operational since 1998.

   Since May 2002, the protocol described by this text has been
   operating on IANA port nut/3493 running over TCP.

      |  Historically, the previous number 3305 was a relic of the
      |  original code's ancestry, and conflicted with other services.
      |  UDP support was dropped in July 2003.  It had been deprecated
      |  for some time and was only capable of the simplest query
      |  commands as authentication is impossible over a UDP socket.

1.3.  Requirements Language

   The key words "MUST", "MUST NOT", "REQUIRED", "SHALL", "SHALL NOT",
   "SHOULD", "SHOULD NOT", "RECOMMENDED", "MAY", and "OPTIONAL" in this
   document are to be interpreted as described in RFC 2119 [RFC2119].

1.4.  Comments

   The editor welcomes comments.  Technical matters should be addressed
   to the NUT Project (2.6)'s mailing list [mailinglist].  Editorial
   matters may be addressed directly to the editor, email:
   "ietf@rogerprice.org" .

Price                   Expires 7 September 2021                [Page 4]
Internet-Draft           UPS management protocol              March 2021

2.  Terminology

   The following technical terms appear in this text.

2.1.  Attachment Daemon

   The Attachment Daemon talks to the UPS units or other power devices
   often through a Driver (2.2) specific to the hardware model and the
   connection medium, e.g.  USB, serial.  It maintains an abstracted
   view of the hardware through the use of hardware statuses 2.10.  A
   Management Daemon (2.5) may consult the abstracted view using the
   commands described in this text.  Although the term "Attachment
   Daemon" includes the word "daemon" nothing requires that it be
   implemented as a detached software service.  An Attachment Daemon
   must support statuses (2.10) OB and OL.  It must also support status
   LB if the UPS provides such information.

2.2.  Driver

   A Driver is that part of an Attachment Daemon which is specific to
   the hardware, the connection medium and the connection protocol, e.g.
   USB, serial.  In current practice the Attachment Daemon has a driver
   for each hardware interface type it supports.  Although this text
   considers the driver to be part of the Attachment Daemon, current
   practice is to see it as a separate software unit running as an
   unattached daemon "in front of" the Attachment Daemon.  The protocol
   between the driver and the attachment daemon may use [RFC1628].

2.3.  Event

   An Event is a change in UPS status (2.10) detected by the Management
   Daemon (2.5)

2.4.  Instant Command

   A command which when sent to the Attachment Daemon (2.1) causes the
   hardware to immediately perform a function.  For example "INSTCMD
   su700 test.panel.start"

2.5.  Management Daemon

   The Management Daemon is primarily responsible for managing the
   hardware and the system reaction to power loss.  Using commands sent
   to the Attachment Daemon (2.1) it follows the status of the UPS and
   determines when UPS events occur.  It takes decisions based on the
   events, such a calling for a system shutdown.  Although the term
   includes the word "daemon" nothing requires that it be implemented as
   a detached software service.  The Management Daemon may also provide

Price                   Expires 7 September 2021                [Page 5]
Internet-Draft           UPS management protocol              March 2021

   administrative functions such as a graphic interface to view the
   hardware activity.

2.6.  NUT (Network UPS Tools) Project

   The primary goal of the NUT project [NUT] is to provide support for
   Power Devices, such as Uninterruptible Power Supplies.  The Project
   has been in operation since 1998 with a major rework in 2003.  It
   operates through a mailing list [mailinglist] and a web site [NUT].

2.7.  Primary

   When a power device such as a UPS unit supplies power to more than
   one system, the one to which the data lead is connected is known as
   the primary.  The others are secondary.  See figure 4.  Common
   current practice for system administrators is to consider the
   Management Daemon (2.5) in the primary to be the Primary Management
   Daemon which is in charge of the shutdown of all the systems powered
   by the UPS.  The Primary Management Daemon sets status symbol "FSD"
   to order the secondaries to shut down.

      |  Note: Historically, the primary was known as the "Master".

2.8.  Secondary

   When a hardware device such as a UPS unit supplies power to more than
   one system, the one to which the data lead is connected is known as
   the Primary (2.7).  The other are secondaries.  There is no
   Attachment Daemon (2.1) in a secondary.  See figure 4.  Common
   current practice for system administrators is to consider the
   Management Daemon (2.5) in a secondary to be a Secondary Management
   Daemon which understands status symbol "FSD" as an order to shut
   down.

      |  Note: Historically, the secondary was known as the "Slave".

2.9.  Session

   The Management Daemon (2.5) may open a session with a specified
   device such as a UPS known to the Attachment Daemon (2.1).  The
   session structure provides for audit and security as well as access
   to mission critical UPS functions.  For example good practice
   requires a password protection for an instant command (2.4) which
   turns off a UPS outlet.  Other than the commands and responses used,
   the details of session management are outside the scope of this text.

Price                   Expires 7 September 2021                [Page 6]
Internet-Draft           UPS management protocol              March 2021

2.10.  UPS status

   The status of a hardware device such as a UPS unit is a symbolic
   description of the state of the unit.  It consists of a space
   separated list of symbols from the set {"ALARM" "BOOST" "BYPASS"
   "CAL" "CHRG" "COMM" "DISCHRG" "FSD" "LB" "NOCOMM" "OB" "OFF" "OVER"
   "RB" "RB" "TEST" "TRIM"}.  The symbols "TICK" and "TOCK" are
   experimental additions to the status and are not in common current
   practice.  See the appendix (5.1) which specifies each of these
   symbols.  The statuses "LB", "OB" and "OL" are considered fundamental
   and are supported for all units.  Other statuses depend on the
   feature set of the hardware.

2.11.  UPS variable

   The features provided by each UPS are represented by variables giving
   the current value attached to that feature.  The UPS variable is an
   abstraction of the UPS hardware configuration and activity maintained
   by the Attachment Daemon (2.1).  See the appendix (Section A.1,
   Paragraph 1) which provides a non exhaustive list of variables.  For
   example the variable "battery.charge" contains the current charge of
   the UPS battery as a percentage value.

3.  Protocol overview

   Figure 1 shows a reference configuration in which the command/
   response protocol applies.  The UPS shown is representative of all
   power devices,

                                                    "The client"
                   ,--------------,               ,--------------,
         ,-----,   |     UPS      | <-Commands    |     UPS      |
         | UPS |---|  Attachment  |---------------|  Management  |
         |     |===|    Daemon    |   Responses-> |    Daemon    |
         /-----\   '--------------'               '--------------'
                    UPS Attachment                 UPS Management
                        System        Network          System

                     Figure 1: Reference Configuration

   The reference configuration in figure 1 shows a single UPS unit which
   has a power supply link ("===") and a data link ("---") attached to a
   system running an Attachment Daemon (2.1).  The UPS provides power
   supply protection to the system running the Attachment Daemon.  The
   data link may use [RFC1628].

Price                   Expires 7 September 2021                [Page 7]
Internet-Draft           UPS management protocol              March 2021

   In practice there may be more than one UPS unit, and a unit may
   provide power protection to more than one system.  The figure also
   shows a single Management Daemon (2.5).  In practice there may be
   more than one Management Daemon, and any one Management Daemon may
   manage more than one UPS Attachment Daemon.

   The protocol applies to connections between the Management Daemon and
   the Attachment daemon.  The Management Daemon is known as the
   *client*.  It sends commands over TCP to the Attachment Daemon and
   receives responses over TCP from that daemon.

   The two daemons may run in the same system, or may be connected
   through a local or wide area network.  In simple cases, as shown in
   figure 2, the Attachment Daemon (2.1) and the Management Daemon (2.5)
   are in the same system, the one protected by the UPS.  The commands
   and responses are exchanged through an internal loopback interface.

                                                   "The client"
                     ,--------------------,---------------------,
           ,-----,   |     UPS       <-Commands        UPS      |
           | UPS |---|  Attachment        |         Management  |
           |     |===|    Daemon       Responses->    Daemon    |
           /-----\   '--------------------'---------------------'
                                       Internal
                                       loopback
                       UPS Attachment and Management System

              Figure 2: Simplified single-system configuration

   The reference configuration does not require any specific design.
   For example figure 3 shows an arrangement in which the Attachment
   Daemon (2.1) is closely associated with, or even included in the UPS
   system setup.  This is becoming more prevalent with the availability
   of low cost processors able to run the Attachment Daemon (2.1)

                                                 "The client"
            ,-----,------------,               ,--------------,
            |     |    UPS     | <-Commands    |     UPS      |
            | UPS - Attachment |---------------|  Management  |
            |     |   Daemon   |   Responses-> |    Daemon    |
            /-----'------------\               '--------------'
               UPS Attachment                   UPS Management
                   System           Network          System

              Figure 3: UPS and Attachment Daemon integration

Price                   Expires 7 September 2021                [Page 8]
Internet-Draft           UPS management protocol              March 2021

   As the power requirements for processors decrease, it is becoming
   increasingly common to use a single UPS to protect multiple systems
   as shown in figure 4.  However there is only one data line ("---")
   from the UPS to the Primary (2.7) system.  The others have only power
   connections ("===") to the UPS, and each is known as a Secondary
   (2.8).  A Secondary (2.8) does not run an Attachment Daemon (2.1), it
   connects over a network to the Attachment Daemon (2.1) in the
   primary.  Figure 4 shows the Attachment Daemon (2.1) and the primary
   Management Daemon (2.5) in the same system.  This is common practice
   but it is not a technical requirement.

                                          "The client"
               ,--------------------,---------------------,
     ,-----,   |     UPS       <-Commands      Primary    |
     |     |---|  Attachment        |         Management  |   Primary
     |     |===|    Daemon       Responses->    Daemon    |
     |     |   '--------------------'---------------------'
     | UPS |            ^
     |     |            '<-Commands---Responses->,
     |     |                                     v
     |     |            ,--------------,-----------------,
     |     |============|              |     Secondary   |
     /-----\            |              |     Management  |   Secondary
                        |              |       Daemon    |
                        '--------------'-----------------'

                  Figure 4: UPS protects multiple systems

4.  Protocol specification

   This specification includes only the commands and their responses.
   An implementation of the Attachment Daemon (2.1) has an internal
   state machine, and some complex implementations of the Management
   Daemon (2.5) include an internal state machine; for example to assist
   the system shutdown of a complex installation.  However the
   management protocol used between them is effectively stateless.  Most
   responses received by the Management Daemon (2.5) are sufficient in
   themselves, and at most require knowledge of the previous response to
   that command.  See for example table (5.2) which maps the new
   "ups.status" response and the previous "ups.status" response to an
   Event (5.2) which is taken as the basis for Management Daemon (2.5)
   action.

4.1.  Notation used in this specification

   The character set used for commands and responses is UTF-8 but
   current practice is to limit the character set used to the single
   byte UTF-8 characters 0-127.

Price                   Expires 7 September 2021                [Page 9]
Internet-Draft           UPS management protocol              March 2021

   Multi-word elements are contained within U+0022 QUOTATION MARK
   characters for easier parsing.  E.g.  ""UPS on fire"".  Embedded
   quotation marks are escaped with U+005C REVERSE SOLIDUS \ often known
   as backslashes.  Embedded backslashes are also escaped by
   representing them as \\.

   Commands and responses have no leading or trailing whitespace, and
   are terminated with a single new line character U+000A LINE FEED
   (LF).

   White space within commands and responses is reduced to one U+0020
   (SP) SPACE.

4.2.  Commands

4.2.1.  "FSD"

   A Management Daemon (2.5) which is Primary (2.7) and has the required
   authority, uses this command to set status symbol "FSD" in the
   Attachment Daemon (2.1).  Current practice uses the symbol to tell
   each Secondary (2.8) system to shut down.  It has the same value as
   the pair of status symbols "OB" "LB".

   Command: "FSD <upsname>"           The response is: "OK FSD-SET" if
   the command is successful.

   Current practice requires that an application introduce security
   controls in its session management to defend against abusive use of
   this command.  The details are outside the scope of this text.

4.2.2.  "GET"

   Retrieve a single response from the server.  The possible sub-
   commands are:

4.2.2.1.  "CMDDESC"

   Command: "GET CMDDESC <upsname> <cmdname>"

   Response: CMDDESC <upsname> <cmdname> "<description>"

   For example: "GET CMDDESC su700 load.on" and response "CMDDESC su700
   load.on "Turn on the load immediately""

   This is like "DESC", but it applies to an instant command (2.4).

Price                   Expires 7 September 2021               [Page 10]
Internet-Draft           UPS management protocol              March 2021

4.2.2.2.  "DESC"

   Command: "GET DESC <upsname> <varname>"

   Response: "DESC <upsname> <varname> "<description>""

   where <description> is a string that gives a brief explanation of the
   named variable.  The Attachment Daemon (2.1) may return "Unavailable"
   if the file which provides this description is not installed.

   For example command "GET DESC su700 ups.status" and response "DESC
   su700 ups.status "UPS status""

4.2.2.3.  "NUMLOGINS"

   Command: "GET NUMLOGINS <upsname>"

   Response: "NUMLOGINS <upsname> <value>"

   where <value> is the number of clients which have succeeded in doing
   a LOGIN to this UPS.

   For example command "GET NUMLOGINS su700" and response "NUMLOGINS
   su700 1"

   This information may be needed by the Management Daemon (2.5) to
   determine how many clients are still connected when starting the
   system shutdown process.

4.2.2.4.  "TYPE"

   Command: "GET TYPE <upsname> <varname>"

   Response: "TYPE <upsname> <varname> <type>..."

   where <type> can be one or more of the following tokens.  Multiple
   types may be returned.

   For example command "GET TYPE su700 input.transfer.low" and response
   "TYPE su700 input.transfer.low ENUM"

Price                   Expires 7 September 2021               [Page 11]
Internet-Draft           UPS management protocol              March 2021

       +==============+============================================+
       |     Type     |                  Meaning                   |
       +==============+============================================+
       | RW           | This variable may be set to another value  |
       |              | with command "SET"                         |
       +--------------+--------------------------------------------+
       | ENUM         | An enumerated type, which supports         |
       |              | specific pre-determined values             |
       +--------------+--------------------------------------------+
       | STRING:n     | This is a string of maximum length "n"     |
       +--------------+--------------------------------------------+
       | RANGE        | This is a number, either integer or float, |
       |              | comprised in the range which may be seen   |
       |              | with the command LIST RANGE (4.2.5.4)      |
       +--------------+--------------------------------------------+
       | NUMBER       | This is a single numeric value, either     |
       |              | integer or float                           |
       +--------------+--------------------------------------------+

                          Table 1: Variable types

   Notes:

   *  "ENUM", "STRING:n" and "RANGE", are usually associated with "RW",
      but not always.  The default <type>, when omitted, is numeric, so
      either integer or float.  Each Driver (2.2) is then responsible
      for handling values as either integer or float.

   *  Current practice is to represent floating point values using
      locale "C.utf8" which is a decimal (base 10) US English-based
      representation.  Hexadecimal, exponents, and comma for thousands
      separator are not allowed.  For example: "1200.20" is valid, while
      "1,200.20" and "1200,20" are invalid.

4.2.2.5.  "UPSDESC"

   Command: "GET UPSDESC <upsname>"

   Response: "UPSDESC <upsname> "<description>""

   where <description> is defined by the Attachment Daemon (2.1)
   configuration.  If it is not set, current practice is for the
   Attachment Daemon (2.1) to return "Unavailable".

   For example command "GET UPSDESC su700" and response "UPSDESC su700
   "Development box""

Price                   Expires 7 September 2021               [Page 12]
Internet-Draft           UPS management protocol              March 2021

   This can be used to provide human-readable descriptions instead of a
   cryptic "upsname@hostname" string.

4.2.2.6.  "VAR"

   Command: "GET VAR <upsname> <varname>"

   Response: "VAR <upsname> <varname> "<value>""

   For example command "GET VAR su700 ups.status" and response "VAR
   su700 ups.status "OB LB""

4.2.3.  "HELP"

   Return a list of the commands supported by the Attachment Daemon
   (2.1).  This command is intended for human as well as program use.

   Command "HELP"

   For example, the following command line sequence executed on an
   Attachment Daemon (2.1):

   netcat localhost 3493
   HELP
   Commands: HELP VER GET LIST SET INSTCMD LOGIN LOGOUT
             LOGOUT USERNAME PASSWORD STARTTLS

4.2.4.  "INSTCMD"

   Send an instant command (2.4) to the UPS.

   Command: "INSTCMD <upsname> <cmdname>"           The response is:
   "OK"

   where "<upsname>" is the name of the UPS and "<cmdname>" is the
   instant command (2.4) to be issued to that UPS.

   For example the command: "INSTCMD su700 test.panel.start" and the
   response "OK"

4.2.5.  "LIST"

   The "LIST" commands all produce a response with a common container
   format.  The response will begin with "BEGIN LIST" and then repeat
   the initial query.  A list then follows, with as many lines as are
   necessary.  The response ends with "END LIST" followed by the initial
   query.

Price                   Expires 7 September 2021               [Page 13]
Internet-Draft           UPS management protocol              March 2021

   The formatting may seem a bit redundant, but it makes a different
   form of client possible.  A client can send a "LIST" query and then
   go off and wait for the response.  When it arrives, the Management
   Daemon (2.5) doesn't need a complicated state machine to remember
   which list is which.

   The possible subcommands are:

4.2.5.1.  "CLIENT"

   The command calls for the Attachment Daemon (2.1) to report all the
   current Management Daemon (2.5) clients of a given UPS.  See command
   LOGIN (4.2.6).

   Command: "LIST CLIENT <upsname>"           The response is

   BEGIN LIST CLIENT <upsname>
   CLIENT <upsname> <client_IP_address>
   ...
   END LIST CLIENT <upsname>

   For example, the command "LIST CLIENT ups1" and the response:

   BEGIN LIST CLIENT ups1
   CLIENT ups1 ::1
   CLIENT ups1 198.51.100.2
   END LIST CLIENT ups1

4.2.5.2.  "CMD"

   The command calls for the Attachment Daemon (2.1) to report a list of
   each UPS instant command (2.4) which the Management Daemon (2.5) may
   sent to the Attachment Daemon (2.1).  This instant command (2.4) list
   is the abstracted view of the UPS hardware capabilities.  An
   economical UPS will support few or no instant command (2.4) but a
   professional model should support more.

   Command: "LIST CMD <upsname>"           The response is:

   BEGIN LIST CMD <upsname>
   CMD <upsname> <cmdname>
   ...
   END LIST CMD <cmdname>

   where "<upsname>" is the name of the UPS, and "<cmdname>" is the name
   of the command which may be issued to the UPS.

   For example the command: "LIST CMD su700" and the response:

Price                   Expires 7 September 2021               [Page 14]
Internet-Draft           UPS management protocol              March 2021

   BEGIN LIST CMD su700
   CMD su700 load.on
   CMD su700 test.panel.start
   ...
   END LIST CMD su700

4.2.5.3.  "ENUM"

   The command calls for the Attachment Daemon (2.1) to report the set
   of possible values of a UPS variable which has predetermined values.

   Command: "LIST ENUM <upsname> <varname>"           The response is:

   BEGIN LIST ENUM <upsname> <varname>
   ENUM <upsname> <varname> "<value>"
   ...
   END LIST ENUM <upsname> <varname>

   where "<upsname>" is the name of the UPS, "<varname>" is the UPS
   variable and "<value>" is one of the possible values of the UPS
   variable.  Note that the U+0022 QUOTATION MARK characters are part of
   the response.

   For example the command: "LIST ENUM su700 input.transfer.low" and the
   response:

   BEGIN LIST ENUM su700 input.transfer.low
   ENUM su700 input.transfer.low "103"
   ENUM su700 input.transfer.low "100"
   ...
   END LIST ENUM su700 input.transfer.low

4.2.5.4.  "RANGE"

   The command calls for the Attachment Daemon (2.1) to report the
   interval in which valid values of a UPS variable lie.

   Command: "LIST RANGE <upsname> <varname>"           The response is:

   BEGIN LIST RANGE <upsname> <varname>
   RANGE <upsname> <varname> "<min>" "<max>"
   ...
   END LIST RANGE <upsname> <varname>

   where "<upsname>" is the name of the UPS, "<varname>" is the UPS
   variable and {"<min>","<max>"} is the interval of valid values of the
   UPS variable.  Note that the U+0022 QUOTATION MARK characters are
   part of the response.

Price                   Expires 7 September 2021               [Page 15]
Internet-Draft           UPS management protocol              March 2021

   For example, the command "LIST RANGE su700 input.transfer.low" and
   the response:

   BEGIN LIST RANGE su700 input.transfer.low
   RANGE su700 input.transfer.low "90" "100"
   RANGE su700 input.transfer.low "102" "105"
   ...
   END LIST RANGE su700 input.transfer.low

4.2.5.5.  "RW"

   The command calls for the Attachment Daemon (2.1) to report a list of
   the UPS variables associated with a given UPS which may be read and
   written by the Management Daemon (2.5).  These variables are the
   abstracted view of the UPS hardware capabilities.  An economical UPS
   will support few variables but a professional model should support at
   least the variables which are needed for automatic shutdown and
   restart.

   Command: "LIST RW <upsname>"           The response is:

   BEGIN LIST RW <upsname>
   RW <upsname> <varname> "<value>"
   ...
   END LIST RW <upsname>

   where "<upsname>" is the name of the UPS, "<varname>" is the UPS
   variable and "<value>" is the value of the UPS variable.  Note that
   the U+0022 QUOTATION MARK characters are part of the response.

   For example the command: "LIST RW su700" and the response:

   BEGIN LIST RW su700
   RW su700 output.voltage.nominal "115"
   RW su700 ups.delay.shutdown "020"
   ...
   END LIST RW su700

4.2.5.6.  "UPS"

   Command: "LIST UPS"           The response is:

   BEGIN LIST UPS
   UPS <upsname> "<description>"
   ...
   END LIST UPS

Price                   Expires 7 September 2021               [Page 16]
Internet-Draft           UPS management protocol              March 2021

   where <upsname> is the name of a UPS, and <description> is the value
   of the description maintained by the Attachment Daemon (2.1) if
   available.  It is set to "Unavailable" otherwise.  Note that the
   U+0022 QUOTATION MARK characters are part of the response.

   This command can also be used to determine what values of <upsname>
   are valid before calling other functions on the server.  This is also
   a good way to handle situations where a single Attachment Daemon
   (2.1) supports multiple UPS's.  It is also useful for clients which
   perform a UPS discovery process.

   For example, the response:

   BEGIN LIST UPS
   UPS su700 "Development box"
   END LIST UPS

4.2.5.7.  "VAR"

   Command: "LIST VAR <upsname>"           The response is:

   BEGIN LIST VAR <upsname>
   VAR <upsname> <varname> "<value>"
   ...
   END LIST VAR <upsname>

   where "<upsname>" is the name of the UPS, "<varname>" is the UPS
   variable and "<value>" is the value of the UPS variable.  Note that
   the U+0022 QUOTATION MARK characters are part of the response.

   The response to this command lists the UPS variables available for
   this UPS and their current values.  For example the command "LIST VAR
   su700" and the response:

   BEGIN LIST VAR su700
   VAR su700 ups.mfr "APC"
   VAR su700 ups.mfr.date "10/17/96"
   ...
   END LIST VAR su700

4.2.6.  "LOGIN"

   The Attachment Daemon (2.1) provides facilities to limit access to
   the UPS unit(s) to which it is attached.  A system administrator
   performs a login to open a Session (2.9) and gain access to a UPS,
   and a logout when the Session (2.9) is no longer needed.

Price                   Expires 7 September 2021               [Page 17]
Internet-Draft           UPS management protocol              March 2021

   Command: "LOGIN <upsname>"           The response is "OK" if the
   login is successful.

      |  Current practice is for the command "LOGIN" to allow connection
      |  to the Attachment Daemon (2.1).  If there are two UPS units
      |  attached to the Attachment Daemon (2.1) logging into the first
      |  will automatically log into the second as well.

4.2.7.  "LOGOUT"

   The Attachment Daemon (2.1) provides facilities to limit access to
   the UPS unit(s) to which it is attached.  A system administrator
   performs a login to open a Session (2.9) and gain access, and a
   logout when the Session (2.9) is no longer needed.  The command
   "LOGOUT" allows the system administrator to disconnect gracefully.

   Command: "LOGOUT" with the response "OK Goodbye" if the disconnection
   was successful.

4.2.8.  "PASSWORD"

   The Management Daemon (2.5) specifies a password required to enter a
   Session (2.9) with the Attachment Daemon (2.1).

   Command: "PASSWORD <password>"           The response is: "OK" if the
   command is successful.

4.2.9.  "PRIMARY"

   The Attachment Daemon (2.1) uses this command within a Session (2.9)
   to claim that it is a Primary (2.7) and has the required authority to
   perform such critical actions as setting status symbol "FSD".

   Command: "PRIMARY <upsname>" with response: "OK" if the Attachment
   Daemon (2.1) does have such authority.

   where "<upsname>" is the name of the UPS.

      |  Note: Historically, this command was known as "MASTER".

4.2.10.  "PROTVER"

   Return the implementation version of the command/response protocol
   used by the Attachment Daemon (2.1).  This command is intended for
   human as well as program use.

   Command "PROTVER"

Price                   Expires 7 September 2021               [Page 18]
Internet-Draft           UPS management protocol              March 2021

   For example, the following command line sequence in the Attachment
   Daemon (2.1):

   netcat localhost 3493
   PROTVER
   1.2

      |  Note: Historically, this command was known as "NETVER" and
      |  current practice is to use "NETVER" instead of "PROTVER"

4.2.11.  "SET"

   The command calls for the Attachment Daemon (2.1) to set a UPS
   variable to a given value.  Whether this has an effect on the UPS
   hardware is specific to the Driver (2.2) and the UPS model.

   Command: "SET VAR <upsname> <varname> "<value>""           The
   response is: "OK"

   where "<upsname>" is the name of the UPS, "<varname>" is the UPS
   variable and "<value>" is the value to be assigned to the UPS
   variable.  Note that the U+0022 QUOTATION MARK characters are part of
   the command.

   For example the command: "SET VAR su700 ups.id "My UPS"" and the
   response "OK"

4.2.12.  "STARTTLS"

   The client tells the Attachment Daemon (2.1) to switch to TLS
   encrypted communication.  When the client receives "OK" it also
   switches to TLS encryption.

   Command: "STARTTLS"           The response is: "OK STARTTLS" if the
   command is successful.

4.2.13.  "USERNAME"

   The Session (2.9) may require that the Management Daemon (2.5)
   identifies a "UPS management user" who has been authorized to send
   commands to the Attachment Daemon (2.1).  In current practice, this
   "user" is specific to UPS management and is not a user of the
   operating system.  The technique for specifying this UPS management
   user is specific to the implementation, and may be done with a
   configuration file.

   Command: "USERNAME <username>"           The response is "OK" if the
   command is successful.

Price                   Expires 7 September 2021               [Page 19]
Internet-Draft           UPS management protocol              March 2021

4.2.14.  "VER"

   Return the implementation version of the Attachment Daemon (2.1).
   This command is intended for human as well as program use.

   Command "VER"

   For example, the following command line sequence:

   netcat localhost 3493
   VER
   Network UPS Tools upsd 2.7.4 - http://www.networkupstools.org/

4.3.  Error responses

   Error responses have the following format:

   ERR <error-name> [<extra>]

   where "<error-name>" is a single word token taken from the 27
   characters A-Z and HYPHEN-MINUS U+002D.  Implementations may if
   needed add an additional optional "<extra>".  Current practice does
   not make use of this possibility.

   The "<error-name>" may have one of the following values:

    +==============================+=================================+
    |   The error name token       |             Meaning             |
    |        "<error-name>"        |                                 |
    +==============================+=================================+
    | ACCESS-DENIED                | The client's host and/or        |
    |                              | authentication details          |
    |                              | (username, password) are not    |
    |                              | sufficient to execute the       |
    |                              | requested command.              |
    +------------------------------+---------------------------------+
    | ALREADY-LOGGED-IN            | The client has already sent a   |
    |                              | successful "LOGIN" command for  |
    |                              | a given UPS and can't do it     |
    |                              | again.                          |
    |                              |                                 |
    |                              | Note: Current practice is to    |
    |                              | impose a limit of one "LOGIN"   |
    |                              | record per connection.  If      |
    |                              | there are two UPS's attached to |
    |                              | the Attachment Daemon (2.1),    |
    |                              | logging into one of them        |

Price                   Expires 7 September 2021               [Page 20]
Internet-Draft           UPS management protocol              March 2021

    |                              | automatically logs into the     |
    |                              | other as well.  See command     |
    |                              | LOGIN (4.2.6).                  |
    +------------------------------+---------------------------------+
    | ALREADY-SET-PASSWORD         | The client has already supplied |
    |                              | a PASSWORD and is attempting to |
    |                              | repeat the command in the same  |
    |                              | Session (2.9).                  |
    +------------------------------+---------------------------------+
    | ALREADY-SET-USERNAME         | The client has already supplied |
    |                              | a USERNAME, and is attempting   |
    |                              | to repeat the command within    |
    |                              | the same Session (2.9).         |
    +------------------------------+---------------------------------+
    | ALREADY-SSL-MODE             | TLS/SSL mode is already enabled |
    |                              | on this connection, so the      |
    |                              | Attachment Daemon (2.1) can't   |
    |                              | start it again.                 |
    +------------------------------+---------------------------------+
    | CMD-NOT-SUPPORTED            | The specified UPS doesn't       |
    |                              | support the instant command     |
    |                              | (2.4) command.                  |
    +------------------------------+---------------------------------+
    | DATA-STALE                   | The Attachment Daemon (2.1) is  |
    |                              | connected to the Driver (2.2)   |
    |                              | for the UPS, but that driver    |
    |                              | isn't providing regular updates |
    |                              | or has specifically marked the  |
    |                              | data as stale.  Current         |
    |                              | practice is for the Attachment  |
    |                              | Daemon (2.1) to refuse to       |
    |                              | provide the Management Daemon   |
    |                              | (2.5) with variables on stale   |
    |                              | units to avoid false readings.  |
    |                              |                                 |
    |                              | This generally means that the   |
    |                              | Driver (2.2) is running, but it |
    |                              | has lost communication with the |
    |                              | hardware.  Check the physical   |
    |                              | connection to the equipment.    |
    +------------------------------+---------------------------------+
    | DRIVER-NOT-CONNECTED         | The Attachment Daemon (2.1)     |
    |                              | can't perform the requested     |
    |                              | command, since the Driver (2.2) |
    |                              | for that UPS is not connected.  |
    |                              | This usually means that the     |
    |                              | driver is not running, or if it |
    |                              | is, is misconfigured.           |

Price                   Expires 7 September 2021               [Page 21]
Internet-Draft           UPS management protocol              March 2021

    +------------------------------+---------------------------------+
    | FEATURE-NOT-CONFIGURED       | This instance of the Attachment |
    |                              | Daemon (2.1) hasn't been        |
    |                              | configured properly to allow    |
    |                              | the requested feature to        |
    |                              | operate.  In current practice   |
    |                              | this error response is possible |
    |                              | only for command "STARTTLS".    |
    +------------------------------+---------------------------------+
    | FEATURE-NOT-SUPPORTED        | This instance of Attachment     |
    |                              | Daemon (2.1) does not support   |
    |                              | the requested feature.  In      |
    |                              | current practice this error     |
    |                              | response is possible only for   |
    |                              | command "STARTTLS".             |
    +------------------------------+---------------------------------+
    | INSTCMD-FAILED               | The Attachment Daemon (2.1)     |
    |                              | failed to deliver the instant   |
    |                              | command (2.4) request to the    |
    |                              | Driver (2.2).  No further       |
    |                              | information is available to the |
    |                              | client.  This typically         |
    |                              | indicates a dead or broken      |
    |                              | driver.                         |
    +------------------------------+---------------------------------+
    | INVALID-ARGUMENT             | The client sent an argument to  |
    |                              | a command which is not          |
    |                              | recognized or is otherwise      |
    |                              | invalid in this context.  This  |
    |                              | is typically caused by sending  |
    |                              | a valid command such as "GET"   |
    |                              | with an invalid subcommand.     |
    +------------------------------+---------------------------------+
    | INVALID-PASSWORD             | The client sent an invalid      |
    |                              | password.                       |
    +------------------------------+---------------------------------+
    | INVALID-USERNAME             | The client sent an invalid      |
    |                              | username.                       |
    +------------------------------+---------------------------------+
    | INVALID-VALUE                | The value specified in the      |
    |                              | request is not valid.  This     |
    |                              | usually applies to a "SET" of   |
    |                              | an "ENUM" type which is using a |
    |                              | value not in the list of        |
    |                              | allowed values.                 |
    +------------------------------+---------------------------------+
    | PASSWORD-REQUIRED            | The command requires a password |
    |                              | for authentication, but the     |

Price                   Expires 7 September 2021               [Page 22]
Internet-Draft           UPS management protocol              March 2021

    |                              | client hasn't provided one.     |
    +------------------------------+---------------------------------+
    | READONLY                     | The requested variable in a     |
    |                              | "SET" command is not writable.  |
    +------------------------------+---------------------------------+
    | SET-FAILED                   | The Attachment Daemon (2.1)     |
    |                              | failed to deliver the set       |
    |                              | request to the Driver (2.2).    |
    |                              | This is similar to "INSTCMD-    |
    |                              | FAILED".                        |
    +------------------------------+---------------------------------+
    | TOO-LONG                     | The requested value in a "SET"  |
    |                              | command is too long.            |
    +------------------------------+---------------------------------+
    | UNKNOWN-COMMAND              | The Attachment Daemon (2.1)     |
    |                              | doesn't recognize the command.  |
    +------------------------------+---------------------------------+
    | UNKNOWN-UPS                  | The UPS specified in the        |
    |                              | request is not known to the     |
    |                              | Attachment Daemon (2.1).  This  |
    |                              | usually means that it didn't    |
    |                              | match anything in the           |
    |                              | Attachment Daemon (2.1)         |
    |                              | configuration.                  |
    +------------------------------+---------------------------------+
    | USERNAME-REQUIRED            | The command requires a username |
    |                              | for authentication, but the     |
    |                              | client hasn't provided one.     |
    +------------------------------+---------------------------------+
    | VAR-NOT-SUPPORTED            | The specified UPS doesn't       |
    |                              | support the UPS variable (2.11) |
    |                              | in the command.                 |
    +------------------------------+---------------------------------+

                         Table 2: Error responses

5.  Statuses and Events

5.1.  Status symbols

   These symbols resume the abstracted view of the UPS hardware
   maintained by the Attachment Daemon (2.1).  The variable "ups.status"
   contains one or more space-separated status symbols which together
   describe the UPS state at that instant.  In current practice the
   Management Daemon (2.5) will poll variable "ups.status" every 5
   seconds with a command such as "GET VAR su700 ups.status" and
   response "VAR su700 ups.status "OB LB"" to discover changes in the
   UPS status.  These changes will indicate UPS events.

Price                   Expires 7 September 2021               [Page 23]
Internet-Draft           UPS management protocol              March 2021

     +=========+====================================================+
     |  Symbol |                      Meaning                       |
     +=========+====================================================+
     | ALARM   | The UPS reports that it requires intervention.     |
     +---------+----------------------------------------------------+
     | BOOST   | The UPS has determined the voltage level of the    |
     |         | public supply is too low, and is boosting it to    |
     |         | the required level.  The UPS continues to supply   |
     |         | the protected system from the public supply.       |
     +---------+----------------------------------------------------+
     | BYPASS  | The UPS is feeding current directly from the       |
     |         | public supply to the protected system.  The backup |
     |         | facilities are disconnected.  This state allows    |
     |         | maintenance personnel to change the batteries      |
     |         | without interrupting the protected system.         |
     +---------+----------------------------------------------------+
     | CAL     | The UPS is calibrating itself, for example to      |
     |         | determine at what charge the "LB" status is raised |
     |         | or lowered.                                        |
     +---------+----------------------------------------------------+
     | CHRG    | The UPS battery is charging.  This usually implies |
     |         | that the UPS also has status "OL", but may not be  |
     |         | the case if the UPS also has status "OFF".         |
     |         |                                                    |
     |         | Note: "OL" does not imply "CHRG" if the battery is |
     |         | floating.                                          |
     +---------+----------------------------------------------------+
     | COMM    | The Attachment Daemon (2.1) has effective contact  |
     |         | with the UPS.                                      |
     +---------+----------------------------------------------------+
     | DISCHRG | The UPS battery is discharging.  This usually      |
     |         | implies that the UPS also has status "OB", but may |
     |         | not be the case if the UPS also has status "OFF".  |
     |         |                                                    |
     |         | Note: "OB" does not imply "DISCHRG" if the battery |
     |         | is floating.                                       |
     +---------+----------------------------------------------------+
     | FSD     | This "Forced Shut Down" status signals that the    |
     |         | final shutdown sequence has begun.                 |
     +---------+----------------------------------------------------+
     | LB      | Low Battery.  The battery level of the UPS is      |
     |         | below a chosen limit.  The UPS may be in status OL |
     |         | or OB.                                             |
     +---------+----------------------------------------------------+
     | NOCOMM  | The Attachment Daemon (2.1) has no effective       |
     |         | contact with the UPS.                              |
     +---------+----------------------------------------------------+
     | OB      | On Battery.  The UPS is offline, taking energy     |

Price                   Expires 7 September 2021               [Page 24]
Internet-Draft           UPS management protocol              March 2021

     |         | from it's battery.  The battery is discharging.  A |
     |         | UPS must have status "OB" or "OL", otherwise it is |
     |         | deemed dead.                                       |
     +---------+----------------------------------------------------+
     | OFF     | The UPS is in state "Off".  It does not react to   |
     |         | failure in the public power supply.  The exact     |
     |         | meaning depends on the model.                      |
     +---------+----------------------------------------------------+
     | OL      | OnLine.  The UPS is online, receiving energy from  |
     |         | the public supply.  The battery is charging.  A    |
     |         | UPS must have status "OB" or "OL", otherwise it is |
     |         | deemed dead.                                       |
     +---------+----------------------------------------------------+
     | OVER    | Overloaded.  The UPS reports that the load on it   |
     |         | is beyond it's normal operating maximum.           |
     +---------+----------------------------------------------------+
     | RB      | Replace battery.  The UPS reports that it's        |
     |         | battery/batteries should be replaced.              |
     +---------+----------------------------------------------------+
     | TEST    | Under test.  The UPS is currently undergoing a     |
     |         | test, which may have been called for manually or   |
     |         | internally.                                        |
     +---------+----------------------------------------------------+
     | TICK    | Heartbeat.  A software UPS in the Attachment       |
     |         | Daemon (2.1) provides a regular signal monitored   |
     |         | by the Management Daemon (2.5) as a way of         |
     |         | verifying effective end-to-end management.  "TICK" |
     |         | and "TOCK" are companions.                         |
     +---------+----------------------------------------------------+
     | TOCK    | Heartbeat.  See "TICK"                             |
     +---------+----------------------------------------------------+
     | TRIM    | The UPS has determined that the voltage level of   |
     |         | the public supply is too high, and is reducing it  |
     |         | to the required level.  The UPS continues to       |
     |         | supply the protected system from the public        |
     |         | supply.                                            |
     +---------+----------------------------------------------------+

                       Table 3: UPS status symbols

Price                   Expires 7 September 2021               [Page 25]
Internet-Draft           UPS management protocol              March 2021

5.2.  Events

   A Management Daemon (2.5) deduces the occurrence of a UPS Event from
   a change in the UPS status (2.10) received from the Attachment Daemon
   (2.1).  The following table summarizes the process.  A status of
   "none" means that the status symbol is not present in the variable
   "ups.status".  In current practice, the variable "ups.status" is
   retrieved every 5 seconds.  The "old" status is therefore the
   previous value retrieved 5 seconds ago.

   Current practice is for the Management Daemon (2.5) to assign names
   to certain events.  These is shown in the table in parentheses.

   +=======+=========+===============++=========+========+=============+
   |Old    | New     |Event          || Old     | New    |Event        |
   |status | status  |               || status  | status |             |
   +=======+=========+===============++=========+========+=============+
   |none   | ALARM   |Alarm on       || ALARM   | none   |Alarm off    |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | BOOST   |Boosting       || BOOST   | none   |Not boosting |
   |       |         |voltage        ||         |        |             |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | BYPASS  |Bypass on      || BYPASS  | none   |Bypass off   |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | CAL     |Calibrating    || CAL     | none   |Not          |
   |       |         |               ||         |        |calibrating  |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | CHRG    |Charging       || CHRG    | none   |Not charging |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | COMM    |UPS            || COMM    | none   |[Note 5]     |
   |       |         |communicating  ||         |        |             |
   |       |         |("COMMOK")     ||         |        |             |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | DISCHRG |Discharging    || DISCHRG | none   |Not          |
   |       |         |               ||         |        |discharging  |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | FSD     |System shutdown|| FSD     | none   |Shutdown     |
   |       |         |("FSD")        ||         |        |abandoned    |
   |       |         |("SHUTDOWN")   ||         |        |[Note 1]     |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | LB      |Low battery    || LB      | none   |Battery not  |
   |       |         |[Note 2]       ||         |        |low          |
   |       |         |("LOWBATT")    ||         |        |             |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | NOCOMM  |UPS dead?      || NOCOMM  | none   |[Note 5]     |
   |       |         |[Note 5]       ||         |        |             |
   |       |         |("COMMBAD")    ||         |        |             |
   |       |         |("NOCOMM")     ||         |        |             |

Price                   Expires 7 September 2021               [Page 26]
Internet-Draft           UPS management protocol              March 2021

   +-------+---------+---------------++---------+--------+-------------+
   |none   | OFF     |UPS turned off || OFF     | none   |UPS not      |
   |       |         |               ||         |        |turned off   |
   +-------+---------+---------------++---------+--------+-------------+
   |OB     | OL      |Receiving wall || OL      | OB     |Wall power   |
   |       |         |power          ||         |        |lost         |
   |       |         |("ONLINE")     ||         |        |("ONBATT")   |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | OVER    |UPS overloaded || OVER    | none   |Overload gone|
   +-------+---------+---------------++---------+--------+-------------+
   |none   | RB      |Replace battery|| RB      | none   |Replacement  |
   |       |         |("REPLBATT")   ||         |        |canceled     |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | TEST    |Test starts    || TEST    | none   |Test finished|
   +-------+---------+---------------++---------+--------+-------------+
   |none   | TICK    |Heartbeat event|| TICK    | none   |No heartbeat |
   |       |         |[Note 4]       ||         |        |[Note 4]     |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | TOCK    |Heartbeat event|| TOCK    | none   |No heartbeat |
   |       |         |[Note 4]       ||         |        |[Note 4]     |
   +-------+---------+---------------++---------+--------+-------------+
   |none   | TRIM    |Trimming       || TRIM    | none   |Not trimming |
   |       |         |voltage        ||         |        |             |
   +-------+---------+---------------++---------+--------+-------------+

                Table 4: Event deduction from status changes

   Notes

   1.  Current practice does not include this event.
   2.  If the status "OB" is present, current practice takes Management
       Daemon (2.5) reception of "LB" as an order to perform an
       emergency system shutdown.
   3.  (For future use)
   4.  The use of a software defined UPS to provide a heartbeat is
       experimental and is not part of common current practice.
   5.  Current practice is: if the UPS has not responded for 15 seconds,
       the Management Daemon (2.5) assumes that the UPS is "dead"
       ("NOCOMM"), and if the last known "OL"/"OB" status was "OB" a
       system shutdown ("FSD") is called for.

6.  IANA Considerations

   // Ed: See Guidelines for Writing an IANA Considerations Section in
   // RFCs [RFC8126]

   This text raises five matters which fall within IANA Considerations:

Price                   Expires 7 September 2021               [Page 27]
Internet-Draft           UPS management protocol              March 2021

   1.  The namespaces occupied by the protocol commands (4.2) described
       in this text.

   2.  The namespaces occupied by the protocol responses (4.3) described
       in this text.

   3.  The namespace occupied by UPS status (2.10) names,

   4.  The namespace occupied by UPS variable (2.11) names,

   5.  The port name and port number used to manage UPS units.

6.1.  Namespaces used by Command, Responses, Statuses and Variables

   Current NUT Project (2.6) experience after more than 20 years is that
   the UPS management area advances slowly, and that there are few
   requests to modify or extend the Commands, Responses, Statuses and
   Variables.  When this does occur, the NUT Project (2.6) has been able
   to settle the matter without difficulty in the project mailing list.
   It is therefore proposed to not burden IANA with this namespace
   management and to continue with the current process in which the
   project in its mailing list acts as a Working Group,

6.2.  Port name and number used to manage UPS units

6.2.1.  Current situation

   See the IANA [Registry] for the latest situation.

6.2.1.1.  Port nut/3493

   In 2002 IANA assigned port nut/3493 to project lead Russell Kroll,
   and updated the assignment to the NUT Project (2.6) itself in 2020.

6.2.1.2.  Port ups/401

   In 2008 IANA assigned ups/401 "Uninterruptible Power Supply" to Mr.
   Charles Bennett as both assignee and contact.  We have been unable to
   find any protocol document or other published activity report for
   this port.  Mr. Bennett himself died in 2015, see obituary [Bennett].
   Since his email address was registered by IANA as "bennettc@ohio.edu"
   it is possible that the University of Ohio is a successor in
   interest.  The editor tried to contact the IT support department of
   the university by email and telephone but was rejected.
   // Ed: My non-contact was Mr. Keith Brock, IT Support Senior
   // Specialist, brock@ohio.edu +1 740 597 2136

Price                   Expires 7 September 2021               [Page 28]
Internet-Draft           UPS management protocol              March 2021

6.2.2.  Request to IANA

   The NUT Project (2.6) is mindful of IANA's position

   |  that the applicant MUST NOT use the requested port in
   |  implementations deployed for use on the public Internet prior to
   |  the completion of the assignment

   in clause 8.1.1 of [RFC6335] and makes the following requests to
   assist the security migration strategy described in Section 7.4,
   Paragraph 1.

   1.  The NUT Project (2.6) wishes to use the existing UPS Management
       Protocol as described in this text on existing port ups/401 for
       full security access to the Attachment Daemon (2.1), i.e. command
       "STARTTLS" must be issued, accepted and applied.

   2.  The NUT Project (2.6) requests that IANA consider transferring
       port ups/401 to the NUT Project (2.6) and would appreciate IANA
       Expert advice on this matter.

7.  Security Considerations

   A functioning power supply is vital to a computing system.  The
   Management Daemon (2.5) is able to shut down a working system and
   it's power supply: this raises multiple security issues.  Most of
   these are well known IT issues concerning system protection and
   disaster recovery, and are beyond the scope of this text.  However
   the protocol itself has security considerations:

   1.  It should not be possible for non-authorized agents to open
       sessions and send mission-critical commands such as "FSD
       <upsname>" to the Attachment Daemon (2.1).
   2.  It should not be possible to intercept the traffic between the
       Attachment Daemon (2.1) and the Management Daemon (2.5).

   The following facilities address these requirements.

7.1.  Agent verification

   The protocol provides commands "LOGIN" and "PASSWORD" which allow a
   Management Daemon (2.5) to authenticate itself to the Attachment
   Daemon (2.1).  The password needs protection from sniffing: This is
   done by encrypting the traffic.

Price                   Expires 7 September 2021               [Page 29]
Internet-Draft           UPS management protocol              March 2021

7.2.  Encryption

   The protocol provides command "STARTTLS" which calls on the
   Attachment Daemon (2.1) to support TLS encryption of the
   communication.  If this command is accepted, the Management Daemon
   (2.5) must also encrypt.

   At present the command "STARTTLS" is too frequently refused, and
   traffic proceeds unencrypted, with for example plain text
   transmission of passwords.

7.3.  Current security practice

   Experience over the last 20 years shows that new UPS management
   software releases are not frequent, and when installed, stay
   unmodified for some years.  This is probably because UPS management
   is a mature hardware dependent activity.  A limited number of system
   administrators have access to the UPS hardware and software and tend
   to assume a certain "security by obscurity" since many installations
   have a configuration as shown in figure 5 which uses port nut/3493
   between the two daemons running in the same system.  The traffic is
   often not encrypted, and when encrypted uses deprecated early
   versions of SSL/TLS.

           ,-----,   ,--------------------,---------------------,
           | UPS |---|  Attachment   <-Commands     Management  |
           |     |===|    Daemon       Responses->    Daemon    |
           /-----\   '--------------------'---------------------'
                        Listens on
                       port nut/3493
                       for localhost

                Figure 5: Common single-system configuration

   This situation is now changing as low cost processors become
   available, costing significantly less than a UPS unit.  This
   evolution makes it interesting to shift to a configuration as shown
   in figure 6, but it also exacerbates the security weakness of figure
   5 since the traffic between the daemons is now over an exposed
   network.

            ,-----,------------,               ,--------------,
            | UPS - Attachment | <-Commands    |  Management  |
            |     |   Daemon   |   Responses-> |    Daemon    |
            /-----'------------\               '--------------'
                    Listens on
                   port nut/3493

Price                   Expires 7 September 2021               [Page 30]
Internet-Draft           UPS management protocol              March 2021

             Figure 6: Integration of UPS and Attachment Daemon

7.4.  Security needs

   UPS management needs to move to a more secure practice in which all
   traffic is encrypted, but this cannot be imposed by a wave of the
   hand.  The ideal would be an easy-to-follow migration plan which
   provides the required encryption but tolerates the slow moving
   updates of the UPS software.  A possible technique introduces shims
   between the Attachment Daemon (2.1) and the network, and between the
   network and the Management Daemon (2.5) as shown in figure 7.  These
   shims provide TLS support, allowing the Attachment Daemon (2.1) and
   Management Daemon (2.5) to continue temporarily without native TLS.
   The technique has been successfully tested, but the principal
   difficulty is that the shims make use of a second port which is not
   currently available.

                    TLS shim listens     TLS shim listens
                       on port ??          on port 3493
       ,-----,------------,----,               ,----,--------------,
       | UPS - Attachment |TLS | <-STARTTLS    | TLS|  Management  |
       |     |   Daemon   |shim|         OK--> |shim|    Daemon    |
       /-----'------------'----\               '----'--------------'
               Listens on
             port nut/3493

            Figure 7: Shims provide TLS support during migration

7.4.1.  Attachment Daemon shim

   The shim in front of the Attachment Daemon (2.1) listens to incoming
   traffic on a port to be specified.  When it receives the command
   "STARTTLS" it

   1.  Returns "OK" to the client and sets up TLS encapsulation.
   2.  Does not send "STARTTLS" to the Attachment Daemon (2.1) port
       nut/3493.

   All other commands and responses are passed through.

7.4.2.  Management Daemon shim

   The shim in front of the Management Daemon (2.5) listens for incoming
   traffic on port nut/3493.  When it receives the command "STARTTLS" it

   1.  Returns "FEATURE-NOT-CONFIGURED" to the client.
   2.  Sends "STARTTLS" to the Attachment Daemon (2.1) on a port to be
       specified.

Price                   Expires 7 September 2021               [Page 31]
Internet-Draft           UPS management protocol              March 2021

   All other commands and responses are passed through.

8.  Acknowledgments

   This text is based on the NUT Project (2.6) documentation
   [developerguide].  The editor acknowledges the work of Charles
   Lepple, Arjen de Korte, Arnaud Quette, Jim Klimov, Russell Kroll, and
   many others who contribute to the nut-upsuser mailing list
   [mailinglist].

   The source for the text is marked up using an SGML DTD [SGML] and an
   XML meta-DTD as defined by HyTime Annex A [HyTimeA].  The "sgmlnorm"
   [sgmlnorm] program generates XML which program "xml2rfc" [RFC7991]
   uses to prepare the text.  The editor acknowledges the help received
   from Carsten Bormann and Julian Reschke in the xml2rfc mailing list.

9.  Normative References

   [RFC2119]  Bradner, S., "Key words for use in RFCs to Indicate
              Requirement Levels", BCP 14, RFC 2119,
              DOI 10.17487/RFC2119, March 1997,
              <https://www.rfc-editor.org/info/rfc2119>.

10.  Informative References

   [Bennett]  "Charles Bennett Obituary", Publisher: Jagers and Sons
              Funeral Home, 24 Morris Ave., Athens OH,
              <https://www.legacy.com/obituaries/name/charles-bennett-
              obituary?pid=174356861>.

   [developerguide]
              "Network UPS Tools (NUT) Project Developer Guide",
              <https://networkupstools.org/docs/developer-guide.chunked/
              ar01s09.html>.

   [HyTimeA]  "International Standard ISO/IEC 10744 -- Hypermedia/Time-
              based Structuring Language, Annex A, SGML Extended
              Facilities", ISO/IEC JTC 1/SC 34 Document description and
              processing languages, 1997.

   [mailinglist]
              "Network UPS Tools (NUT) Project Mailing List",
              <https://alioth-lists.debian.net/cgi-bin/mailman/listinfo/
              nut-upsuser>.

   [NUT]      "Network UPS Tools (NUT) Project",
              <https://www.networkupstools.org>.

Price                   Expires 7 September 2021               [Page 32]
Internet-Draft           UPS management protocol              March 2021

   [Registry] "Service Name and Transport Protocol Port Number
              Registry", Publisher: IANA,
              <https://www.iana.org/assignments/service-names-port-
              numbers/service-names-port-numbers.xhtml>.

   [RFC1628]  Case, J., Ed., "UPS Management Information Base",
              RFC 1628, DOI 10.17487/RFC1628, May 1994,
              <https://www.rfc-editor.org/info/rfc1628>.

   [RFC6335]  Cotton, M., Eggert, L., Touch, J., Westerlund, M., and S.
              Cheshire, "Internet Assigned Numbers Authority (IANA)
              Procedures for the Management of the Service Name and
              Transport Protocol Port Number Registry", BCP 165,
              RFC 6335, DOI 10.17487/RFC6335, August 2011,
              <https://www.rfc-editor.org/info/rfc6335>.

   [RFC7991]  Hoffman, P., "The "xml2rfc" Version 3 Vocabulary",
              RFC 7991, December 2016,
              <https://www.rfc-editor.org/info/rfc7991>.

   [RFC8126]  Cotton, M., Leiba, B., and T. Narten, "Guidelines for
              Writing an IANA Considerations Section in RFCs", BCP 26,
              RFC 8126, DOI 10.17487/RFC8126, June 2017,
              <https://www.rfc-editor.org/info/rfc8126>.

   [SGML]     Goldfarb, Charles F., "The SGML Handbook",
              ISBN 0-19-853737-9, 1990.

   [sgmlnorm] Clark, James., "SGMLNORM An SGML System Conforming to
              International Standard ISO 8879 -- Standard Generalized
              Markup Language", <http://www.jclark.com/sp/sgmlnorm.htm>.

Appendix A.  Variables and Instant Commands

A.1.  UPS variables

   The UPS variables represent the abstracted state of the UPS unit.
   The number of variables depends on the sophistication of the product.
   Those shown here are a typical example.  An implementation of a
   Management Daemon (2.5) acting as a utility program may provide a
   listing of the variables available, as well as acting on them.
   // Ed: NUT: upsc

Price                   Expires 7 September 2021               [Page 33]
Internet-Draft           UPS management protocol              March 2021

    +===============================+============+====================+
    |            Variable           |  Typical   |      Default       |
    |                               |   value    |    description     |
    +===============================+============+====================+
    | battery.charge                | 100        | "Battery charge    |
    |                               |            | (percent of full)" |
    +-------------------------------+------------+--------------------+
    | battery.charge.low            | 20         | "Remaining battery |
    |                               |            | level when UPS     |
    |                               |            | switches to LB     |
    |                               |            | (percent)"         |
    +-------------------------------+------------+--------------------+
    | battery.runtime               | 1481       | "Battery runtime   |
    |                               |            | (seconds)"         |
    +-------------------------------+------------+--------------------+
    | battery.type                  | PbAc       | "Battery           |
    |                               |            | chemistry"         |
    +-------------------------------+------------+--------------------+
    | device.mfr                    | WhizBang   | ""                 |
    +-------------------------------+------------+--------------------+
    | device.model                  | Economy    | ""                 |
    |                               | 1700       |                    |
    +-------------------------------+------------+--------------------+
    | device.serial                 | 1234567890 | ""                 |
    +-------------------------------+------------+--------------------+
    | device.type                   | ups        | ""                 |
    +-------------------------------+------------+--------------------+
    | driver.name                   | usbhid-ups | "Driver name"      |
    +-------------------------------+------------+--------------------+
    | driver.parameter.lowbatt      | 37         | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.offdelay     | 30         | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.ondelay      | 40         | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.pollfreq     | 30         | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.pollinterval | 2          | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.port         | auto       | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.synchronous  | no         | "Driver parameter: |

Price                   Expires 7 September 2021               [Page 34]
Internet-Draft           UPS management protocol              March 2021

    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.parameter.vendorid     | 0999       | "Driver parameter: |
    |                               |            | <name>"            |
    +-------------------------------+------------+--------------------+
    | driver.version                | 2.7.4      | "Driver version -  |
    |                               |            | NUT release"       |
    +-------------------------------+------------+--------------------+
    | driver.version.data           | HID 1.39   | ""                 |
    +-------------------------------+------------+--------------------+
    | driver.version.internal       | 0.41       | "Internal driver   |
    |                               |            | version"           |
    +-------------------------------+------------+--------------------+
    | input.transfer.high           | 264        | "High voltage      |
    |                               |            | transfer point     |
    |                               |            | (V)"               |
    +-------------------------------+------------+--------------------+
    | input.transfer.low            | 184        | "Low voltage       |
    |                               |            | transfer point     |
    |                               |            | (V)"               |
    +-------------------------------+------------+--------------------+
    | outlet.1.desc                 | PowerShare | "Outlet            |
    |                               | Outlet 1   | description"       |
    +-------------------------------+------------+--------------------+
    | outlet.1.id                   | 2          | "Outlet system     |
    |                               |            | identifier"        |
    +-------------------------------+------------+--------------------+
    | outlet.1.status               | on         | "Outlet switch     |
    |                               |            | status"            |
    +-------------------------------+------------+--------------------+
    | outlet.1.switchable           | no         | "Outlet switch     |
    |                               |            | ability"           |
    +-------------------------------+------------+--------------------+
    | outlet.2.desc                 | PowerShare | "Outlet            |
    |                               | Outlet 2   | description"       |
    +-------------------------------+------------+--------------------+
    | outlet.2.id                   | 3          | "Outlet system     |
    |                               |            | identifier"        |
    +-------------------------------+------------+--------------------+
    | outlet.2.status               | on         | "Outlet switch     |
    |                               |            | status"            |
    +-------------------------------+------------+--------------------+
    | outlet.2.switchable           | no         | "Outlet switch     |
    |                               |            | ability"           |
    +-------------------------------+------------+--------------------+
    | outlet.desc                   | Main       | "Outlet            |
    |                               | Outlet     | description"       |
    +-------------------------------+------------+--------------------+

Price                   Expires 7 September 2021               [Page 35]
Internet-Draft           UPS management protocol              March 2021

    | outlet.id                     | 1          | "Outlet system     |
    |                               |            | identifier"        |
    +-------------------------------+------------+--------------------+
    | outlet.power                  | 25         | ""                 |
    +-------------------------------+------------+--------------------+
    | outlet.switchable             | no         | "Outlet switch     |
    |                               |            | ability"           |
    +-------------------------------+------------+--------------------+
    | output.frequency.nominal      | 50         | "Nominal output    |
    |                               |            | frequency (Hz)"    |
    +-------------------------------+------------+--------------------+
    | output.voltage                | 230.0      | "Output voltage    |
    |                               |            | (V)"               |
    +-------------------------------+------------+--------------------+
    | output.voltage.nominal        | 230        | "Nominal output    |
    |                               |            | voltage (V)"       |
    +-------------------------------+------------+--------------------+
    | ups.beeper.status             | enabled    | "UPS beeper        |
    |                               |            | status"            |
    +-------------------------------+------------+--------------------+
    | ups.delay.shutdown            | 20         | "Interval to wait  |
    |                               |            | after shutdown     |
    |                               |            | with delay command |
    |                               |            | (seconds)"         |
    +-------------------------------+------------+--------------------+
    | ups.delay.start               | 30         | "Interval to wait  |
    |                               |            | before             |
    |                               |            | (re)starting the   |
    |                               |            | load (seconds)"    |
    +-------------------------------+------------+--------------------+
    | ups.firmware                  | 02         | "UPS firmware"     |
    +-------------------------------+------------+--------------------+
    | ups.load                      | 20         | "Load on UPS       |
    |                               |            | (percent of full)" |
    +-------------------------------+------------+--------------------+
    | ups.mfr                       | WhizBang   | "UPS manufacturer" |
    +-------------------------------+------------+--------------------+
    | ups.model                     | Economy    | "UPS model"        |
    |                               | 1700       |                    |
    +-------------------------------+------------+--------------------+
    | ups.power.nominal             | 1700       | "UPS power rating  |
    |                               |            | (VA)"              |
    +-------------------------------+------------+--------------------+
    | ups.productid                 | ffff       | "Product ID for    |
    |                               |            | USB devices"       |
    +-------------------------------+------------+--------------------+
    | ups.serial                    | 000000000  | "UPS serial        |
    |                               |            | number"            |

Price                   Expires 7 September 2021               [Page 36]
Internet-Draft           UPS management protocol              March 2021

    +-------------------------------+------------+--------------------+
    | ups.status                    | OL         | "UPS status"       |
    +-------------------------------+------------+--------------------+
    | ups.timer.shutdown            | 0          | "Time before the   |
    |                               |            | load will be       |
    |                               |            | shutdown           |
    |                               |            | (seconds)"         |
    +-------------------------------+------------+--------------------+
    | ups.timer.start               | 0          | "Time before the   |
    |                               |            | load will be       |
    |                               |            | started (seconds)" |
    +-------------------------------+------------+--------------------+
    | ups.vendorid                  | 0999       | "Vendor ID for USB |
    |                               |            | devices"           |
    +-------------------------------+------------+--------------------+

                       Table 5: Typical UPS Variables

A.2.  UPS readable and writable variables

   Some of the features of a UPS are represented by variables which may
   be tuned by the user.  The following variables are typical of such
   tunable features.  The precise list depends on the model of UPS.  An
   implementation of a Management Daemon (2.5) acting as a utility
   program may provide a listing of the variables available, as well as
   acting on them.
   // Ed: NUT: upsrw

Price                   Expires 7 September 2021               [Page 37]
Internet-Draft           UPS management protocol              March 2021

     +========================+============+=========================+
     |        Variable        |  Typical   |   Default description   |
     |                        |   value    | provided as response to |
     |                        |            |  the command "GET DESC" |
     +========================+============+=========================+
     | battery.charge.low     | 20         | "Remaining battery      |
     |                        |            | level when UPS switches |
     |                        |            | to LB (percent)"        |
     +------------------------+------------+-------------------------+
     | input.transfer.high    | 264        | "High voltage transfer  |
     |                        |            | point (V)"              |
     +------------------------+------------+-------------------------+
     | input.transfer.low     | 184        | "Low voltage transfer   |
     |                        |            | point (V)"              |
     +------------------------+------------+-------------------------+
     | outlet.1.desc          | PowerShare | "Outlet description"    |
     |                        | Outlet 1   |                         |
     +------------------------+------------+-------------------------+
     | outlet.2.desc          | PowerShare | "Outlet description"    |
     |                        | Outlet 2   |                         |
     +------------------------+------------+-------------------------+
     | outlet.2.switchable    | no         | "Outlet switch ability" |
     +------------------------+------------+-------------------------+
     | outlet.desc            | Main       | "Outlet description"    |
     |                        | Outlet     |                         |
     +------------------------+------------+-------------------------+
     | outlet.power           | 25         | "Description            |
     |                        |            | unavailable"            |
     +------------------------+------------+-------------------------+
     | output.voltage.nominal | 230        | "Nominal output voltage |
     |                        |            | (V)"                    |
     +------------------------+------------+-------------------------+
     | ups.delay.shutdown     | 20         | "Interval to wait after |
     |                        |            | shutdown with delay     |
     |                        |            | command (seconds)"      |
     +------------------------+------------+-------------------------+
     | ups.delay.start        | 30         | "Interval to wait       |
     |                        |            | before (re)starting the |
     |                        |            | load (seconds)"         |
     +------------------------+------------+-------------------------+

            Table 6: Typical readable and writable UPS Variables

Price                   Expires 7 September 2021               [Page 38]
Internet-Draft           UPS management protocol              March 2021

A.3.  UPS Instant Commands

   Some of the features of a UPS are actions which may be ordered by the
   user.  The following variables represent such actions.  The precise
   list depends on the model of UPS.  An implementation of a Management
   Daemon (2.5) acting as a utility program may provide a listing of the
   variables available, as well as acting on them.
   // Ed: NUT: upscmd

      +==================+==========================================+
      |     Command      |                 Meaning                  |
      +==================+==========================================+
      | beeper.disable   | Disable the UPS beeper                   |
      +------------------+------------------------------------------+
      | beeper.enable    | Enable the UPS beeper                    |
      +------------------+------------------------------------------+
      | beeper.mute      | Temporarily mute the UPS beeper          |
      +------------------+------------------------------------------+
      | load.off         | Turn off the load immediately            |
      +------------------+------------------------------------------+
      | load.off.delay   | Turn off the load with a delay (seconds) |
      +------------------+------------------------------------------+
      | load.on          | Turn on the load immediately             |
      +------------------+------------------------------------------+
      | load.on.delay    | Turn on the load with a delay (seconds)  |
      +------------------+------------------------------------------+
      | shutdown.return  | Turn off the load and return when power  |
      |                  | is back                                  |
      +------------------+------------------------------------------+
      | shutdown.stayoff | Turn off the load and remain off         |
      +------------------+------------------------------------------+
      | shutdown.stop    | Stop a shutdown in progress              |
      +------------------+------------------------------------------+

                     Table 7: Typical Instant Commands

Appendix B.  Change Log

   This section is to be removed before publishing as an RFC.

   // Ed: To be removed on publication.

B.1.  Changes in version 01

   1.  There is exactly one newline (4.1) at the end of commands and
       responses.
   2.  Added descriptions to variables in Annex (A).

Price                   Expires 7 September 2021               [Page 39]
Internet-Draft           UPS management protocol              March 2021

   3.  Added clause Event (5.2).

B.2.  Changes in version 02

   1.  Extended acknowledgments.
   2.  Added reference to possible use of RFC1628 between driver and
       Attachment Daemon (2.1).
   3.  Clarified response to command "LIST CLIENT".

Author's Address