Network Working Group                                    J. Quittek, Ed.
Internet-Draft                                                 R. Winter
Intended status: Informational                                  T. Dietz
Expires: January 12, 2012                                NEC Europe Ltd.
                                                               B. Claise
                                                         M. Chandramouli
                                                     Cisco Systems, Inc.
                                                           July 11, 2011


                   Requirements for Energy Management
                    draft-ietf-eman-requirements-04

Abstract

   This document defines requirements for standards specifications for
   energy management.  Defined requirements concern monitoring functions
   as well as control functions.  Covered functions include
   identification of powered entities, monitoring of their power state,
   power inlets, power outlets, actual power, consumed energy, and
   contained batteries.  Further included is control of powered
   entities' power supply and power state.  This document does not
   specify the features that must be implemented by compliant
   implementations but rather features that must be supported by
   standards for energy management.

Status of this Memo

   This Internet-Draft is submitted in full conformance with the
   provisions of BCP 78 and BCP 79.

   Internet-Drafts are working documents of the Internet Engineering
   Task Force (IETF).  Note that other groups may also distribute
   working documents as Internet-Drafts.  The list of current Internet-
   Drafts is at http://datatracker.ietf.org/drafts/current/.

   Internet-Drafts are draft documents valid for a maximum of six months
   and may be updated, replaced, or obsoleted by other documents at any
   time.  It is inappropriate to use Internet-Drafts as reference
   material or to cite them other than as "work in progress."

   This Internet-Draft will expire on January 12, 2012.

Copyright Notice

   Copyright (c) 2011 IETF Trust and the persons identified as the
   document authors.  All rights reserved.




Quittek, et al.         Expires January 12, 2012                [Page 1]


Internet-Draft     Requirements for Energy Management          July 2011


   This document is subject to BCP 78 and the IETF Trust's Legal
   Provisions Relating to IETF Documents
   (http://trustee.ietf.org/license-info) in effect on the date of
   publication of this document.  Please review these documents
   carefully, as they describe your rights and restrictions with respect
   to this document.  Code Components extracted from this document must
   include Simplified BSD License text as described in Section 4.e of
   the Trust Legal Provisions and are provided without warranty as
   described in the Simplified BSD License.


Table of Contents

   1.  Introduction . . . . . . . . . . . . . . . . . . . . . . . . .  4
     1.1.   Conventional requirements for energy management . . . . .  4
     1.2.   Specific requirements for energy management . . . . . . .  5

   2.  Terminology  . . . . . . . . . . . . . . . . . . . . . . . . .  6

   3.  General Objectives of Energy Management  . . . . . . . . . . .  8
     3.1.   Power states  . . . . . . . . . . . . . . . . . . . . . .  8
     3.2.   Trade-offs  . . . . . . . . . . . . . . . . . . . . . . .  8
     3.3.   Local and network-wide energy management  . . . . . . . .  8
     3.4.   Energy monitoring . . . . . . . . . . . . . . . . . . . .  9
     3.5.   Overview of energy management requirements  . . . . . . . 10

   4.  Identification of Powered Entities . . . . . . . . . . . . . . 10

   5.  Information on Powered Entities  . . . . . . . . . . . . . . . 11
     5.1.   General information on powered entities . . . . . . . . . 11
     5.2.   Power state . . . . . . . . . . . . . . . . . . . . . . . 12
     5.3.   Power inlet and power outlet  . . . . . . . . . . . . . . 14
     5.4.   Power . . . . . . . . . . . . . . . . . . . . . . . . . . 16
     5.5.   Energy  . . . . . . . . . . . . . . . . . . . . . . . . . 18
     5.6.   Battery State . . . . . . . . . . . . . . . . . . . . . . 19

   6.  Control of Powered Entities  . . . . . . . . . . . . . . . . . 21

   7.  Reporting on Other Powered Entities  . . . . . . . . . . . . . 22

   8.  Controlling Other Powered Entities . . . . . . . . . . . . . . 23
     8.1.   Controlling power states of other powered entities  . . . 23
     8.2.   Controlling power supply of other powered entities  . . . 24

   9.  Security Considerations  . . . . . . . . . . . . . . . . . . . 25

   10. IANA Considerations  . . . . . . . . . . . . . . . . . . . . . 26




Quittek, et al.         Expires January 12, 2012                [Page 2]


Internet-Draft     Requirements for Energy Management          July 2011


   11. Acknowledgements . . . . . . . . . . . . . . . . . . . . . . . 26

   12. Open issues  . . . . . . . . . . . . . . . . . . . . . . . . . 26
     12.1.  Revise security considerations  . . . . . . . . . . . . . 26
     12.2.  High/Low power notifications  . . . . . . . . . . . . . . 26
     12.3.  Power and energy time series? . . . . . . . . . . . . . . 26
     12.4.  Inlet/outlet combinations . . . . . . . . . . . . . . . . 26
     12.5.  Aggregation functions . . . . . . . . . . . . . . . . . . 27
     12.6.  Add a definition of 'demand'  . . . . . . . . . . . . . . 27
     12.7.  IEC references  . . . . . . . . . . . . . . . . . . . . . 27
     12.8.  Standard references for BACNET or MODBUS  . . . . . . . . 27
     12.9.  IEEE 1621 and 802.3az references  . . . . . . . . . . . . 27
     12.10. DC power quality covered by IEC standard? . . . . . . . . 27
     12.11. Introduce 'disconnected from power' as power state  . . . 27
     12.12. Need for basic state 'reduced power'? . . . . . . . . . . 27
     12.13. Local and network-wide energy management  . . . . . . . . 28
     12.14. Do we need entity types?  . . . . . . . . . . . . . . . . 28
     12.15. Power availability mode 'minimum' or 'ready'? . . . . . . 28
     12.16. Is there a need for metering power supply inpedance?  . . 28
     12.17. Confidence in power values  . . . . . . . . . . . . . . . 28
     12.18. Terminology for reporting on other entitites  . . . . . . 28

   13. Informative References . . . . . . . . . . . . . . . . . . . . 29

   Appendix A.  Existing Standards  . . . . . . . . . . . . . . . . . 30
     A.1.   Existing IETF Standards . . . . . . . . . . . . . . . . . 30
       A.1.1.  ENTITY MIB . . . . . . . . . . . . . . . . . . . . . . 30
       A.1.2.  ENTITY STATE MIB . . . . . . . . . . . . . . . . . . . 31
       A.1.3.  ENTITY SENSOR MIB  . . . . . . . . . . . . . . . . . . 31
       A.1.4.  UPS MIB  . . . . . . . . . . . . . . . . . . . . . . . 32
       A.1.5.  POWER ETHERNET MIB . . . . . . . . . . . . . . . . . . 32
       A.1.6.  LLDP MED MIB . . . . . . . . . . . . . . . . . . . . . 33
     A.2.   Existing standards of other bodies  . . . . . . . . . . . 33
       A.2.1.  DMTF . . . . . . . . . . . . . . . . . . . . . . . . . 33
       A.2.2.  OVDA . . . . . . . . . . . . . . . . . . . . . . . . . 33
       A.2.3.  IEEE-ISTO Printer WG . . . . . . . . . . . . . . . . . 33

   Authors' Addresses . . . . . . . . . . . . . . . . . . . . . . . . 34













Quittek, et al.         Expires January 12, 2012                [Page 3]


Internet-Draft     Requirements for Energy Management          July 2011


1.  Introduction

   With rising energy cost and with an increasing awareness of the
   ecological impact of running IT and networking equipment, energy
   management is becoming an additional basic requirement for network
   management systems and frameworks.

   This document defines requirements for standards specifications for
   energy management.  Defined requirements concern monitoring functions
   as well as control functions.  Covered functions include
   identification of powered entities, monitoring of their power state,
   power inlets, power outlets, actual power, consumed energy, and
   contained batteries.  Further included is control of powered
   entities' power supply and power state.  Note that this document does
   not specify the features that must be implemented by compliant
   implementations but rather features that must be supported by
   standards for energy management.

   The main subject of energy management are powered entities that
   consume electric energy.  Powered entities include devices that have
   an IP address and can be addressed directly, such as hosts, routers,
   and middleboxes, as well as devices indirectly connected to an IP
   network, for which a proxy with an IP address provides a management
   interface, for example, devices in a building management
   infrastructure using BACNET or MODBUS protocols.

   The requirements specified in this document explicitly concern the
   standards specification process and not the implementation of
   specified standards.  All requirements in this document must be
   reflected by standards specifications to be developed.  But which of
   the features specified by these standards will be mandatory,
   recommended, or optional for compliant implementations is to be
   defined by the concrete standards track document(s) and not in this
   document.

   This document first discusses general objectives of energy management
   in Section 3.  Requirements for an energy management standard are
   specified in Sections 4 to 8.

1.1.  Conventional requirements for energy management

   The specification of requirements for an energy management standard
   starts with Section 4 addressing the identification of powered
   entities and the granularity of reporting of energy-related
   information.  A standard must support unique identification of
   powered entities.  Furthermore, it must support more than just
   reporting per powered device.  Support is required for also reporting
   energy-related information on individual components of a device or



Quittek, et al.         Expires January 12, 2012                [Page 4]


Internet-Draft     Requirements for Energy Management          July 2011


   subtended devices.  This is why this draft uses the more general term
   "powered entity" rather than "powered device".  A powered entity may
   be a device or a component of a device.

   Section 5 specifies requirements related to monitoring of powered
   entities.  This includes general (type, context) information and
   specific information on power states, power inlets, power outlets,
   power, energy, and batteries.  Control power state and power supply
   of powered entities is covered by requirements specified in
   Section 6.

1.2.  Specific requirements for energy management

   At first glance the rather conventional requirements summarized above
   seem to be all that would be needed for energy management.  But it
   turns out that there are some significant differences between energy
   management and most of the well known conventional network management
   functions.  The most significant difference from many other
   management functions is the need for some devices to report on other
   entities.  There are three major reasons for this.
   o  For monitoring and controlling a particular powered entity in
      general it is not sufficient to communicate with the powered
      entity only, but in many cases also communication with other
      powered entities along the power distribution path may be
      necessary, for example, with power switches and power meters.
      Indeed, there are situations where a power or energy meter is not
      located in the powered entity, but in a different physical
      location.  For example, a Power Distribution Unit (PDU), which
      supplies power for a server connected to a PDU socket, would meter
      the power supplied, while the server may not have the capability
      to measure its power consumption.  A second example is a Power
      over Ethernet port, which provides power to the attached device,
      and which can meter how much power/energy it delivers to the
      attached device.
   o  Energy management often extends its scope beyond powered entities
      with IP network interfaces, for example toward non-IP building
      networks, that are accessed via an IP gateway.  Requirements in
      this document do not fully cover all these networks, but they
      cover means for opening IP network management towards them.
   o  For monitoring of particular powered entities, it is sometimes not
      a scalable approach to communicate directly with all the powered
      entities directly from a central energy management system as the
      number of powered entities keeps increasing.

   This specific issue of energy management and a set of further ones
   are covered by requirements specified in Sections 7 and 8.





Quittek, et al.         Expires January 12, 2012                [Page 5]


Internet-Draft     Requirements for Energy Management          July 2011


2.  Terminology

2.1.  Energy

   the definition of the term energy is to be agreed on in the EMAN WG.

   The term 'energy consumption' is commonly used for both, for
   referring to the amount of consumed energy and also for referring to
   the rate of consuming energy.  In the first case it addresses
   consumed energy measured by joule, watthour, or another energy unit,
   in the second one it addresses power, typically an average power
   measured by watt.

   However, in this document the term "consumed energy" always refers to
   an energy quantity (measured in joule, watthour, etc.) and not to a
   power quantity (measured in watt, etc.).

2.2.  Power

   the definition of the term power is to be agreed on in the EMAN WG.

2.3.  Powered entity

   A powered entity is a consumer of energy that is subject to energy
   management.  In general, all managed physical entities in a
   communication network consume electric energy and thus are subject to
   energy management including particularly energy monitoring and energy
   control.

   A powered entity can be a managed device or a component of a managed
   device, which is monitored or controlled individually.

2.4.  Power state

   Power state of a powered entitiy is defined as a specific settings of
   a powered entitiy that influences its power.  Examples of power
   states of a powered entitiy are on, off, and sleep.

2.5.  Power monitor

   Energy management requires retrieving energy-related information on
   powered entities.  In many cases this information is not available at
   the powered entities themselves, but at other powered entities.  For
   example measurement of power and energy consumption can be conducted
   by power meters at other locations along the power distribution tree
   for the powered entity.

   A power monitor is a module that reports energy-related information



Quittek, et al.         Expires January 12, 2012                [Page 6]


Internet-Draft     Requirements for Energy Management          July 2011


   on powered entities.  A power monitor may be integrated into a
   powered entity or located remotely of the powered entity.  Instances
   of power monitors may report information on, for example, power
   supply, power, and power state of a powered entity.  There may be
   multiple power monitors reporting information on the same powered
   entity.

2.6.  Power inlet

   Powered entities receive power at their power inlets.  Powered
   entities may have multiple inlets, for example, servers with
   redundant power supply.  Examples for power inlets are AC power cords
   of a powered entity or an Ethernet port at which the powered entity
   receives DC Power over Ethernet (PoE).

2.7.  Power outlet

   Powered entities may have means to supply others with electrical
   power.  Power is delivered to other powered entities through power
   outlets.  Power sourcing entities often have more than one power
   outlet.  Examples for power outlets are AC power sockets at a Power
   Distribution Unit (PDU) and Ethernet ports at a Power over Ethernet
   (PoE) Power Sourcing Equipment (PSE), that can supply powered
   entities with DC power using the Ethernet cable.

2.8.  Energy management

   the definition of the term power is to be agreed on in the EMAN WG.

2.9.  Energy management standard

   This document specifies requirements for an energy management
   standard.  This term refers to a collections of documents specifying
   standards for energy-related monitoring and control.  The energy
   management standard specifies means for building energy management
   systems.

   Requirements specified in this document concern the means that an
   energy management standard must provide.  It does not imply that all
   required means must be implemented in all energy standard scenarios.
   Which means and features must be implemented by compliant
   implementations is to be specified by the energy management standard
   itself, not by this requirements document.

   Note that for meeting individual requirements specified in this
   document, new standards are not necessarily required.  It is
   recommended to rather use existing standards than specify new ones.




Quittek, et al.         Expires January 12, 2012                [Page 7]


Internet-Draft     Requirements for Energy Management          July 2011


3.  General Objectives of Energy Management

   The basic objective of energy management is operating communication
   networks and other equipment with minimal amount of energy, while
   maintaining a certain level of service.  A set of use cases for
   energy management can be found in
   [I-D.tychon-eman-applicability-statement].

3.1.  Power states

   One approach to achieve this goal is by setting all powered entities
   to an operational state that results in lower energy consumption, but
   still meets the service level performance objectives.  The sufficient
   performance level may vary over time and can depend on several
   factors.  In principle, there are four basic types of power states
   for a powered entity or for a whole system:
   o  full power state
   o  reduced power states (lower clock rate for processor, lower data
      rate on a link, etc.)
   o  sleep state (not functional, but immediately available)
   o  off state (may imply requiring significant time for becoming
      operational)
   In actual implementations the number of power states and their
   properties vary a lot.  Very simple powered entities may just have
   only the extreme states, full power and off state.  Some
   implementations might use IEEE1621 model of three states on, off, and
   sleep.  However, more granular power states can be implemented with
   many levels of off, sleep, and reduced power states.

3.2.  Trade-offs

   While the general objective of energy management is quite clear, the
   way to attain that goal is often difficult.  In many cases there is
   no way of reducing power consumption without the consequence of a
   potential performance, service, or capacity degradation.  Then a
   trade-off needs to be dealt with between service level objectives and
   energy efficiency.  In other cases a reduction of energy consumption
   can easily be achieved while still maintaining sufficient service
   level performance, for example, by switching powered entities to
   lower power states when higher performance is not needed.

3.3.  Local and network-wide energy management

   Many energy saving functions can be executed locally by a powered
   entitiy.  The basic principle is that a powered entitiy monitors its
   usage and dynamically adapts its energy consumption according to the
   required performance.  It may switch to a sleep state when it is not
   in use at all.  Potential interactions with an energy management



Quittek, et al.         Expires January 12, 2012                [Page 8]


Internet-Draft     Requirements for Energy Management          July 2011


   system for such an entity include the observation of the entity's
   power state and the configuration of power saving policies, for
   example, by setting thresholds for power state changes.

   Energy savings can also be achieved with policies implemented by a
   network management system that controls power states of managed
   entities.  In order to make policy decisions properly, information
   about the energy consumption of powered entities in different power
   states is required.  Often this information is acquired best through
   monitoring.

   Both methods, network-wide and local energy management, have
   advantages and disadvantages.  Most buildings use both of them.  In
   some cases for example, significant energy savings can be achieved by
   simply setting all powered entities in a network to sleep, when the
   network is not needed.  However, in general it is dangerous to set
   all powered entities of a group to the same state, because there is a
   risk that such actions ignore specifics of individual powered
   entities or violate local service level agreements.

3.4.  Energy monitoring

   It should be noted that only monitoring energy consumption and power
   states is obviously not a means to reduce the energy consumption of a
   powered entitiy.  In fact, it is likely to increase the power
   consumption of a powered entitiy slightly because monitoring energy
   may require instrumentation that consumes energy when in use.  And
   also reporting of measured quantities over the network consumes
   energy.  However, the acquired energy consumption and power state
   information is essential for defining energy saving policies and can
   be used as input to power state control loops that in total can lead
   to energy savings.

   Monitoring operational power states and energy consumption can also
   be required for other energy management purposes including but not
   limited to:
   o  investigating power saving potential
   o  evaluating the effectiveness of energy saving policies and
      measures
   o  deriving, implementing, and testing power management strategies
   o  accounting for the total power consumption of a powered entity, a
      network, or a service
   o  predicting a powered entitiy's reliability based on power usage
   o  choosing time of next maintenance cycle for a powered entitiy







Quittek, et al.         Expires January 12, 2012                [Page 9]


Internet-Draft     Requirements for Energy Management          July 2011


3.5.  Overview of energy management requirements

   From the considerations described above the following basic
   management functions appear to be required for energy management:
   o  monitoring power states
   o  monitoring power (energy consumption rate)
   o  monitoring (accumulated) energy consumption
   o  setting power states
   o  setting and enforcing power saving policies

   It should be noted that active power control is complementary (but
   essential) to other energy savings measures such as low power
   electronics, energy saving protocols (for example, IEEE 802.3az),
   energy-efficient device design (for example, sleep and low-power
   modes for individual components of a device), and energy-efficient
   network architectures.  Measurement of energy consumption may also
   provide useful input for developing these technologies.


4.  Identification of Powered Entities

   As already stated Section 1.1, powered entities on which energy-
   related information is provided are identified in a sufficiently
   unique way.  This holds in particular for powered entities that are
   components of managed devices and in case that one powered entity
   reports information on another one, see Section 7.  For powered
   entities that control other powered entities it is important to
   identify the powered entities they control, see Section 8.

   Also stated already in Section 1.1 is the requirement of providing
   means for reporting energy-related information on components of a
   managed device.  An entity in this document may be an entire managed
   device or just a component of it.  Examples of components of interest
   are a hard drive, a battery, or a line card.  For controlling
   entities it may be required to be able to address individual
   components in order to save energy.  For example, server blades can
   be switched off when the overall load is low or line cards at
   switches may be powered down at night times.

   Instrumentation for measuring energy consumption of a device is
   typically more expensive than instrumentation for retrieving the
   devices power state.  It may be a reasonable compromise in many cases
   to provide power state information for all individually switchable
   components of a device separately, while the energy consumption is
   only measured for the entire device.

   Detailed Requirements:




Quittek, et al.         Expires January 12, 2012               [Page 10]


Internet-Draft     Requirements for Energy Management          July 2011


4.1.  Identifying powered entities

   The energy management standard must provide means for uniquely and
   persistently identifying powered entities that are monitored or
   controlled by an energy management system.  Uniqueness must be given
   in a domain that is large enough to avoid collisions of identities at
   potential receivers of monitored information.

4.2.  Identifying components of powered devices

   The energy management standard must provide means for identifying not
   just entire devices as powered entities, but also individual
   components of powered devices.

4.3.  Persistency of Identifiers

   The energy management standard must provide means for indicating
   whether identifiers of powered entities are persistent across a re-
   start of the powered entitiy that provides the identifiers.


5.  Information on Powered Entities

   This section describes energy-related information on powered entities
   for which an energy management standard must provide means for
   retrieving and reporting.

   Note that the fact that an energy management standard provides
   required means does not imply that all of them must be implemented by
   every compliant implementation.  The concrete specification of
   standards based on these requirements may label individual features
   as mandatory, recommended, or optional.

   Required information on powered entities can be structured into six
   groups.  Section 5.1 specifies requirements for general information
   on powered entities, such as type of powered entity or context
   information.  Section 5.2 covers requirements related to entities'
   power states.  Requirements for information on power inlets and power
   outlets of powered entities are specified in Section 5.3.  Monitoring
   of power and energy is covered by Sections 5.4 and 5.5, respectively.
   Finally, Section 5.6 specified requirements for monitoring batteries.

5.1.  General information on powered entities

   For energy management it may be required to understand the role and
   context of a powered entitiy.  When monitoring, it may be helpful to
   group energy consumption per kind of entity.  When controlling and
   setting power states it may be helpful to understand the kind and



Quittek, et al.         Expires January 12, 2012               [Page 11]


Internet-Draft     Requirements for Energy Management          July 2011


   role of a powered entitiy in a network, for example, in order to
   avoid switching off vital network components.

   Detailed Requirements:

5.1.1.  Type of powered entity

   The energy management standard must provide means to retrieve and
   report the type of powered entities according to a standrdized
   classification scheme.

5.1.2.  Context information on powered entities

   The energy management standard must provide means for retrieving and
   reporting context information on powered entities, for example tags
   associated with a powered entity that indicate the powered entitiy's
   role, or importance.

5.1.3.  Grouping of powered entities

   The energy management standard must provide means for grouping
   powered entities, for example, into energy monitoring domains, energy
   control domains, power supply domains, groups of powered entities of
   the same type, etc.

5.2.  Power state

   Many powered entities have a limited number of discrete power states,
   such as, for example, full power, low power, sleep, and off.

   Obviously, there is a need to report the actual power state of a
   powered entitiy.  Beyond that, there is also a requirement for
   standardizing means for retrieving the list of all supported power
   states of a powered entitiy.

   Different standards bodies have already defined their own sets of
   power states for powered entities.  Further organizations are in the
   process of adding more of these sets.  In order to support multiple
   management systems possibly using different power state sets, while
   simultaneously interfacing with a particular powered entity, the
   energy management standard must provide means for supporting multiple
   power state sets used simultaneously at a powered entity.

   Power states have parameters that describe its properties It is
   required to have standardized means for reporting some key
   properties, such as mean power and maximum power of a powered entitiy
   in a certain state.




Quittek, et al.         Expires January 12, 2012               [Page 12]


Internet-Draft     Requirements for Energy Management          July 2011


   There also is a need to report statistics on power states including
   the time spent an the energy consumed in a power state.

   For some network management tasks, it may be desirable to receive
   notifications from powered entities, for example, when the components
   or the entire entity change their power state.

   Detailed Requirements:

5.2.1.  Actual power state

   The energy management standard must provide means for reporting the
   actual power state of a powered entitiy.

5.2.2.  List of supported power states

   The energy management standard must provide means for retrieving the
   list of all potential power states of a powered entitiy.

5.2.3.  Multiple power state sets

   The energy management standard must provide means for supporting
   multiple power state sets simultaneously at a powered entity.

5.2.4.  List of supported power state sets

   The energy management standard must provide means for retrieving the
   list of all power state sets supported by a powered entitiy.

5.2.5.  List of supported power states

   Referring to the "list of supported power state sets" requirement,
   the energy management standard must provide means for retrieving the
   list of all potential power states of a powered entitiy that belong
   to a given power state set.

5.2.6.  Maximum and average power per power state

   The energy management standard must provide means for retrieving the
   maximum power and the average power as a typically static property
   for each supported power state.

5.2.7.  Power state statistics

   The energy management standard must provide means for monitoring
   statistics per power state including at least the total time spent in
   a power state, the number of times a state was entered and the last
   time a state was entered.  More power state statistics are addressed



Quittek, et al.         Expires January 12, 2012               [Page 13]


Internet-Draft     Requirements for Energy Management          July 2011


   by requirement 5.5.3.

5.2.8.  Power state changes

   The energy management standard must provide means for generating a
   notification when the actual power state of a powered entity changes.

5.3.  Power inlet and power outlet

   Powered entities have power inlets at which they are supplied with
   electric power.  Most powered entities just have a single power
   inlet, while some have multiple ones.  Often different power inlets
   are connected to separate power distribution trees.  For energy
   monitoring, it is important information which power inlets a powered
   entitiy has, if power is available at an inlet and which of them are
   actually in use.

   Some powered entities have power outlets for supplying other powered
   entities with electric power.  A powered entitiy may have multiple
   power outlets.  Examples are Power Distribution Units (PDUs) and
   Power over Ethernet (PoE) Power Sourcing Equipment (PSE).

   For identifying and potentially controlling the source of power
   received at an inlet, it may be required to identify the power outlet
   of another powered entity at which the received power is provided.
   Analogously, for each outlet it is of interest to identify the power
   inlets that receive the power provided at a certain outlet.

   Static properties of each power inlet and each power outlet are
   required information for energy management.  Static properties
   include the kind of electric current (Alternating Current (AC) or
   Direct Current (DC)), the nominal voltage, the nominal AC frequency,
   and the number of AC phases.

   Detailed Requirements:

5.3.1.  List of power inlets and power outlets

   The energy management standard must provide means for monitoring the
   list of power inlets and power outlets at a powered entitiy.

5.3.2.  Corresponding power outlet

   The energy management standard must provide means for identifying the
   power outlet that provides the power received at a power inlet.






Quittek, et al.         Expires January 12, 2012               [Page 14]


Internet-Draft     Requirements for Energy Management          July 2011


5.3.3.  Corresponding power inlets

   The energy management standard must provide means for identifying the
   list of power inlets that receive the power provided at a power
   outlet.

5.3.4.  Availability of power

   The energy management standard must provide means for monitoring the
   availability of power at each power inlet and each power outlet.
   This information indicates whether at a power providing outlet power
   supply is switched on or off.

5.3.5.  Use of power

   The energy management standard must provide means for monitoring for
   each power inlet and each power outlet if it is in actual use.  For
   the inlet this means that the powered entitiy actually receives power
   at the inlet.  For the outlet this means that actually power is
   provided to one or more powered entities at the outlet.

5.3.6.  Type of current

   The energy management standard must provide means for reporting the
   type of current (Alternating Current (AC) or Direct Current (DC)) for
   each power inlet and each power outlet of a powered entity.

5.3.7.  Nominal voltage

   The energy management standard must provide means for reporting the
   nominal voltage for each power inlet and each power outlet of a
   powered entity.

5.3.8.  Nominal AC frequency

   The energy management standard must provide means for reporting the
   nominal AC frequency for each power inlet and each power outlet of a
   powered entity.

5.3.9.  number of AC phases

   The energy management standard must provide means for reporting the
   number of AC phases for each power inlet and each power outlet of a
   powered entity.







Quittek, et al.         Expires January 12, 2012               [Page 15]


Internet-Draft     Requirements for Energy Management          July 2011


5.4.  Power

   Power is a quantity measured as instantaneous power or as average
   power over a time interval.  In contrast to power state values, this
   quantity may change continuously.

   Obtaining highly accurate values for power and energy may be costly.
   Often dedicated metering hardware is needed for this purpose.
   Powered entities without the ability to measure their power and
   energy consumption with high accuracy may just report estimated
   values, for example based on load monitoring or even just the entity
   type.

   Depending on how power and energy consumption values are obtained the
   confidence in the reported value and its accuracy may vary.  Powered
   entities reporting such values should qualify the confidence in the
   reported values and quantify the accuracy of measurements.  For
   reporting accuracy, the accuracy classes specified in IEC 62053-21
   [IEC.62053-21] and IEC 62053-22 [IEC.62053-22] should be considered.

   In addition to the plain real power value, also further properties of
   the supplied power are subject to monitoring.  In case of AC power
   supply, there are more power values beyond the real power to be
   reported including the apparent power, the reactive power, and the
   phase angle of the current or the power factor.  For both AC and DC
   power the power quality is also subject of monitoring.  Power quality
   parameters include the actual voltage, the actual frequency, the
   Total Harmonic Distortion (THD) of voltage and current, the impedance
   of an AC phase or of the DC supply.  Power quality monitoring should
   be in line with existing standards, such as [IEC.61850-7-4].

   For some network management tasks, it is required to obtain time
   series of power values (or energy consumption values).  In general
   these could be obtained in many different ways.  It should be avoided
   that such time series can only be obtained by regular polling by the
   energy management system.  Means should be provided to either push
   such values from the place they are available to the management
   system or to have them stored at the powered entitiy for a
   sufficiently long period of time such that a management system can
   retrieve a stored time series of values.

   Detailed Requirements:

5.4.1.  Real power

   The energy management standard must provide means for reporting the
   real power for each power inlet and each power outlet of a powered
   entity.



Quittek, et al.         Expires January 12, 2012               [Page 16]


Internet-Draft     Requirements for Energy Management          July 2011


5.4.2.  Power measurement interval

   The energy management standard must provide means for reporting the
   corresponding time or time interval for which a power value is
   reported.  The power value can be measured at the corresponding time
   or averaged over the corresponding time interval.

5.4.3.  Confidence in power values

   The energy management standard must provide means for reporting the
   confidence in reported power values by indicating the way these
   values have been obtained. for example, by power measurement, by
   estimation based on performance values, or hard coding average power
   values for a powered entity.

5.4.4.  Accuracy of power and energy values

   The energy management standard must provide means for reporting the
   accuracy of reported power values.

5.4.5.  Complex power

   The energy management standard must provide means for reporting the
   complex power for each power inlet and each power outlet of a powered
   entity.  Besides the real power, at least two out of the following
   three quantities need to be reported: apparent power, reactive power,
   phase angle.  The phase angle can be substituted by the power factor.
   In case of AC power supply, means must be provided for reporting the
   complex power per phase.

5.4.6.  Actual voltage and current

   The energy management standard must provide means for reporting the
   actual voltage and actual current for each power inlet and each power
   outlet of a powered entity.  In case of AC power supply, means must
   be provided for reporting the actual voltage and actual current per
   phase.

5.4.7.  Actual AC frequency

   The energy management standard must provide means for reporting the
   actual AC frequency for each power inlet and each power outlet of a
   powered entity.

5.4.8.  Total harmonic distortion

   The energy management standard must provide means for reporting the
   Total Harmonic Distortion (THD) of voltage and current for each power



Quittek, et al.         Expires January 12, 2012               [Page 17]


Internet-Draft     Requirements for Energy Management          July 2011


   inlet and each power outlet of a powered entity.  In case of AC power
   supply, means must be provided for reporting the THD per phase.

5.4.9.  Power supply impedance

   The energy management standard must provide means for reporting the
   impedance of power supply for each power inlet and each power outlet
   of a powered entity.  In case of AC power supply, means must be
   provided for reporting the impedance per phase.

5.4.10.  Time series of power values

   The energy management standard must provide means for collecting time
   series of real power values for each power inlet and for each power
   outlet of a powered entitiy without requiring to regularly poll the
   powered entitiy from an energy management station.  A solution for
   this is that the concerned powered entity or another powered entity
   closely interacting with the concerned powered entity collect time
   series of power values and make them available via push or pull
   mechanisms to receivers of the information.

5.5.  Energy

   Monitoring of electrical energy consumed (or converted) at a powered
   entitiy can be done in various ways.  One is collecting time series
   of power values for the powered entitiy and calculating the consumed
   energy from these values.  An alternative is the powered entity
   itself or another powered entity taking care of energy measurement
   and reporting energy consumption values for certain time intervals.
   Time intervals of interest are the time from the last restart of the
   powered entitiy to the reporting time, the time from another past
   event to the reporting time, or the last given amount of time before
   the reporting time.

   In order to monitor energy consumption in different power states, it
   is useful if powered entities record their energy consumption per
   power state and report these quantities.

   For some network management tasks, it is required to obtain time
   series of energy values.  In general these could be obtained in many
   different ways.  It should be avoided that such time series can only
   be obtained by regular polling by the energy management system.
   Means should be provided to either push such values from the place
   they are available to the management system or to have them stored at
   the powered entitiy for a sufficiently long period of time such that
   a management system can retrieve a stored time series of values.

   Detailed Requirements:



Quittek, et al.         Expires January 12, 2012               [Page 18]


Internet-Draft     Requirements for Energy Management          July 2011


5.5.1.  Energy

   The energy management standard must provide means for reporting the
   consumed energy received at a power input or provided at a power
   outlet of a powered entitiy.  Reports must be made for a clearly
   specified time interval.

5.5.2.  Time intervals

   The energy management standard must provide means for reporting the
   consumed energy of a powered entitiy for certain time intervals.
   o  Reports must be supported for the time interval starting at the
      last restart of the powered entitiy and ending at a certain point
      in time, such as the time when a report was delivered.
   o  Reports must be supported for a sequence of consecutive non-
      overlapping time intervals of fixed size (periodic reports).
   o  Reports must be supported for a sequence of consecutive
      overlapping time intervals of fixed size (periodic reports).
   o  Reports must be supported for an interval of given length ending
      at a certain point in time, such as the time when a report was
      delivered (sliding window)

5.5.3.  Energy per power state

   The energy management standard must provide means for reporting the
   consumed energy individually for each power state.  This extends the
   requirement 5.2.7 on power state statistics.

5.5.4.  Time series of energy values

   The energy management standard must provide means for collecting time
   series of energy values for each power inlet and for each power
   outlet of a powered entitiy without requiring to regularly poll the
   powered entitiy from an energy management station.  A solution for
   this is that the concerned powered entity or another powered entity
   closely interacting with the concerned powered entity collect time
   series of energy values and make them available via push or pull
   mechanisms to receivers of the information.

5.6.  Battery State

   Today more and more powered entities contain batteries that supply
   them with power when disconnected from electrical power distribution
   grids.  Common examples are nomadic and mobile devices, such as
   notebook computers, netbooks, and smart phones.  The status of
   batteries in such an powered entity, particularly the charging status
   is typically controlled by automatic functions that act locally on
   the powered entitiy and manually by users of the powered entity.  In



Quittek, et al.         Expires January 12, 2012               [Page 19]


Internet-Draft     Requirements for Energy Management          July 2011


   addition to this, there is a need to monitor the battery status of
   these entities by network management systems.

   The management requirements discussed above in Sections 5.1 to 5.5
   concern energy-related information on powered entities.  Powered
   entities may be powered devices or components of powered devices.
   Devices containing batteries can be modeled in two ways.  The entire
   device can be modeled as a single powered entity on which energy-
   related information is reported or the battery can be modeled as an
   individual powered entity for which energy-related information is
   monitored individually according to requirements in Sections 5.1 to
   5.5.

   In both cases further information on batteries is of interest for
   energy management, such as the current charge of the battery, the
   number of completed charging cycles, the charging state of the
   battery, and further static and dynamic battery properties.  Also
   desirable is to receive notifications if the charge of a battery
   becomes very low or if a battery needs to be replaced.

   Detailed Requirements:

5.6.1.  Battery charge

   The energy management standard must provide means for reporting the
   current charge of a battery.

5.6.2.  Battery charging state

   The energy management standard must provide means for reporting the
   charging state (charged, discharged, etc.) of a battery.

5.6.3.  Battery charging cycles

   The energy management standard must provide means for reporting the
   number of completed charging cycles of a battery.

5.6.4.  Actual battery capacity

   The energy management standard must provide means for reporting the
   actual capacity of a battery.

5.6.5.  Static battery properties

   The energy management standard must provide means for reporting
   static properties of a battery, including the nominal capacity, the
   number of cells, the nominal voltage, and the battery technology.




Quittek, et al.         Expires January 12, 2012               [Page 20]


Internet-Draft     Requirements for Energy Management          July 2011


5.6.6.  Low battery charge notification

   The energy management standard must provide means for generating a
   notification when a the charge of a battery decreases below a given
   threshold.

5.6.7.  Battery replacement notification

   The energy management standard must provide means for generating a
   notification when the number of charging cycles of battery exceeds a
   given threshold.

5.6.8.  Multiple batteries

   The energy management standard must provide means for meeting
   requirements 5.6.1 to 5.6.7 for each individual battery contained in
   a single powered entity.


6.  Control of Powered Entities

   Many powered entities control their power state locally by self-
   managed dynamic adaptation to the environment.  But other powered
   entities without that capability need interfaces for a energy
   management system to control their power states in order to save
   energy.  Even for self-managed powered entities such interface may be
   required for overruling local policy decisions by global ones from an
   energy management system.

   Power supply is typically not self-managed by powered entities.  And
   controlling power supply is typically not conducted as interaction
   between energy management system and the powered entity itself.  It
   is rather an interaction between the management system and an entity
   providing power at its power outlets.  Still, requirements for power
   state control apply accordingly to power supply control.

   Note that shutting down the power supply abruptly may have severe
   consequences for the powered entity.

   Detailed Requirements:

6.1.  Controlling power states

   The energy management standard must provide means for setting power
   states of powered entities.






Quittek, et al.         Expires January 12, 2012               [Page 21]


Internet-Draft     Requirements for Energy Management          July 2011


6.2.  Controlling power supply

   The energy management standard must provide means for switching power
   supply off or turning power supply on at power outlets providing
   power to one or more powered entity.


7.  Reporting on Other Powered Entities

   As already discussed in the introduction of Section 5, not all
   energy-related information may be available at the concerned powered
   entity.  Such information may be provided by other powered entities,
   such as a Power Distribution Unit (PDU), external power meter, or a
   Power over Ethernet (PoE) Power Sourcing Equipment (PSE).  Some of
   these entities (PDU, PSE) can also control the power provided to the
   other powered entities, while some can just report on the remote
   powered entities (external power meter).  This section covers
   reporting of information (monitoring) only.  See Section 8 for
   requirements on controlling other powered entities.

   There are cases where a power supply unit switches power for several
   powered entities by turning power on or off at a single power outlet
   or where a power meter measures the accumulated power of several
   powered entities at a single power line.  Consequently, it should be
   possible to report that a monitored value does not relate to just a
   single powered entity, but is an accumulated value for a set of
   powered entities.  All of these powered entities belonging to that
   set need to be identified.

   If a powered entity has information about where energy-related
   information on itself can be retrieved, then it would be very useful
   if it has a way to communicate this information to an energy
   management system.  This applies even if the information only
   provides accumulated quantities for several powered entities.

   Detailed Requirements:

7.1.  Reports on other powered entities

   The energy management standard must provide means for a powered
   entitiy to report energy-related information on another powered
   entity.

7.2.  Identity of other powered entities on which is reported

   The energy management standard must provide means for reporting the
   identity of another powered entity on which energy-related
   information is reported.



Quittek, et al.         Expires January 12, 2012               [Page 22]


Internet-Draft     Requirements for Energy Management          July 2011


7.3.  Reporting quantities accumulated over multiple powered entities

   For powered entities reporting single values that are accumulated
   over multiple powered entities, the energy management standard must
   provide means for reporting the list of all powered entities from
   which contributions are included in the accumulated value.

7.4.  List of all powered entities on which is reported

   The energy management standard must provide means for a powered
   entitiy to report the list of all other powered entities on which it
   can report energy-related information.

7.5.  Content of reports on other powered entities

   The energy management standard must provide means for a powered
   entitiy to indicate for each other powered entity on which it can
   provide energy-related information which energy-related information
   can be provided for this powered entity.

7.6.  Indicating source of remote information

   The energy management standard must provide means for a powered
   entity to indicate another powered entity at which energy-related
   information on itself can be retrieved.

7.7.  Indicating source of remote information

   For a powered entity that has another powered entity at which energy-
   related information on itself can be retrieved, the energy management
   standard must provide means for indicating the information that is
   available at other powered entities per other powered entity.


8.  Controlling Other Powered Entities

   This section specifies requirements for controlling power states and
   power supply of powered entities by communicating not with these
   powered entities themselves, but with other powered entities that
   have means for controlling power state or power supply of others.

8.1.  Controlling power states of other powered entities

   Some powered entities may have control of power states of other
   powered entities.  For example a gateway to a building network may
   have means to control the power state of powered entities in the
   building that do not have an IP interface.  For this and similar
   cases means are needed to make this control accessible to the energy



Quittek, et al.         Expires January 12, 2012               [Page 23]


Internet-Draft     Requirements for Energy Management          July 2011


   management system.

   In addition to this, it is required that a powered entitiy that has
   its state controlled by other powered entities has means to report
   the list of these other powered entities.

   Detailed Requirements:

8.1.1.  Control of power states of other powered entities

   The energy management standard must provide means for an energy
   management system to send power state control commands to a powered
   entity that concern the power states of other powered entities than
   the one the command was send to.

8.1.2.  Identity of other power state controlled entities

   The energy management standard must provide means for reporting the
   identity of another powered entity for which the reporting powered
   entity has means to control the power state.

8.1.3.  List of all power state controlled entities

   The energy management standard must provide means for a powered
   entitiy to report the list of all powered entities for which it can
   control the power state.

8.1.4.  List of all power state controllers

   The energy management standard must provide means for a powered
   entitiy that receives commands controlling its power state from other
   powered entities to report the list of all those entities.

8.2.  Controlling power supply of other powered entities

   Some powered entities may have control of the power supply of other
   powered entities, for example, because the other powered entity is
   supplied via a power outlet of the powered entitiy.  For this and
   similar cases means are needed to make this control accessible to the
   energy management system.

   In addition to this, it is very required that a powered entitiy that
   has its supply controlled by other powered entities has means to
   report the list of these other powered entities.

   Detailed Requirements:





Quittek, et al.         Expires January 12, 2012               [Page 24]


Internet-Draft     Requirements for Energy Management          July 2011


8.2.1.  Control of power supply of other powered entities

   The energy management standard must provide means for an energy
   management system to send power supply control commands to a powered
   entity that concern the power supply of other powered entities than
   the one the command was send to.

8.2.2.  Identity of other power supply controlled powered entities

   The energy management standard must provide means for reporting the
   identity of another powered entity for which the reporting powered
   entity has means to control the power supply.

8.2.3.  List of all power supply controlled powered entities

   The energy management standard must provide means for a powered
   entitiy to report the list of all other powered entities for which it
   can control the power supply.

8.2.4.  List of all power supply controllers

   The energy management standard must provide means for a powered
   entitiy that has other powered entities controlling its power supply
   to report the list of all those powered entities.


9.  Security Considerations

   The typical security threats for the management protocol for energy
   monitoring are similar to the ones specified in the SNMP security
   framework.  In other words, from an energy monitoring point of view,
   no additional security requirements have been imposed.

   Link layer discovery mechanisms need to ensure that only the trusted
   powered entities shall be discovered during discovery and detect/
   discard powered entities without a trusted relationship to be
   included among the powered entities for energy monitoring.

   In terms of monitoring, considering that there can be some network
   entities which shall be entitled to collect the measured data on
   behalf of other powered entities, then it is important to
   authenticate and/or authorize such powered entities.  In addition, in
   the case of control of other powered entities, it would be highly
   desirable to have some form of an authentication mechanism to ensure
   that only the designated powered entities shall control the powered
   entities within its control domain.  It should be possible to prevent
   a powered entity which does not have the appropriate authorization
   and authority to control or configure powered entities in its control



Quittek, et al.         Expires January 12, 2012               [Page 25]


Internet-Draft     Requirements for Energy Management          July 2011


   domain/purview.  Secondly, it should be possible to prevent malicious
   powered entities from exercising control over entities.


10.  IANA Considerations

   This document has no actions for IANA.


11.  Acknowledgements

   The authors would like to thank Ralf Wolter for his first essay on
   this draft.  Many thanks to William Mielke, John Parello, Bruce
   Nordman, JinHyeock Choi, Georgios Karagiannis, and Michael Suchoff
   for helpful comments on the draft.


12.  Open issues

12.1.  Revise security considerations

   A discussion of the sensitivity of the content of the monitoring data
   is missing.

12.2.  High/Low power notifications

   For some network management tasks it may be desirable to receive
   notifications from entities when the power of an powered entity
   exceeds or falls below certain thresholds.  Do we want to make this a
   requirement?

   Proposal: added "for example" so that we don't restrict the framework
   to only this notification

12.3.  Power and energy time series?

   We have requirements for reporting of time series of power and energy
   values.  Do we need both or just one of them?  If just one, then
   which one?

12.4.  Inlet/outlet combinations

   How to model the case that an inlet or outlet changes during
   operation from one kind to the other.  An example is a battery that
   receives power at a socket at one time.  Then the socket is an inlet.
   At another time the battery provides power at the same socket.  Then
   it's an outlet.  The same holds for entities with integrated power
   generators.



Quittek, et al.         Expires January 12, 2012               [Page 26]


Internet-Draft     Requirements for Energy Management          July 2011


   One solution would be to introduce a new kind of hybrid in/outlets.
   Another one would be to model the same socket as inlet as well as as
   outlet.  It would appear twice in the list of all inlets and outlets.
   Then received power/energy would be reported under the inlet entry
   and provided power/energy would be reported under the outlet entry.

   These would be two solutions.  What would be the concrete requirement
   behind them?

12.5.  Aggregation functions

   Aggregation functions are not covered (yet).  Are there requirements
   on aggregation?  Which are they?

12.6.  Add a definition of 'demand'

12.7.  IEC references

   References to mentioned IEC standards are missing.  Also these
   references should be double checked.

12.8.  Standard references for BACNET or MODBUS

   Section 1 mentions BACNET or MODBUS as examples for building network
   protocols.  We need references to the standards specifications for
   these protocols.

12.9.  IEEE 1621 and 802.3az references

   A reference to the IEEE 1621 standard is missing in section 3.1 and a
   reference to IEEE 802.3az is missing in section 3.4.  The references
   should be double checked if they are well applicable in the
   respective section.

12.10.  DC power quality covered by IEC standard?

   Is there an IEC standard on DC power quality?

12.11.  Introduce 'disconnected from power' as power state

   We need to introduce the concept of a device being "disconnected"
   from power.  This is a subset of the Off state.  Shall we do it here
   or rather in the framework draft?

12.12.  Need for basic state 'reduced power'?

   Are "full power" and "reduced power" really different basic types of
   power states?  Both may be forms of the on state.  Identifying "full"



Quittek, et al.         Expires January 12, 2012               [Page 27]


Internet-Draft     Requirements for Energy Management          July 2011


   separately is arbitrary.  (For something like a computer, "idle" is
   the most common state so would be the one to call out separately
   rather than "full".)

12.13.  Local and network-wide energy management

   All but first sentence of the third paragraph in section 3.3 seem to
   be true not needed here.  Proposal: remove them.

12.14.  Do we need entity types?

   Or shall we remove Section 5.1.1?

12.15.  Power availability mode 'minimum' or 'ready'?

   Do we need an additional mode for power availability called "minimum"
   or "ready" for power availability in xref target="availability"/>?
   This would reflect a PoE state at which the PSE is ready to serve the
   PD.

12.16.  Is there a need for metering power supply inpedance?



12.17.  Confidence in power values

   Shall we rename "confidence in power values" to "method for
   determining power values"?

12.18.  Terminology for reporting on other entitites

   In Section 7 we need some additional terms here to streamline the
   text (and ultimately our thinking).  Nominations include:
   o  "powered entity" (which may be "self-reporting")
   o  "reporting entity" (can be "self" or "other")
   o  "other entity" (a reporting entity reporting not on itself; likely
      a different term would be better for this)
   o  "controlled entity", "controlling entity" (section 8.1)
   o  "switched entity", "switching entity" (section 8.2)

   Also, there are two cases for an "other entity".  One is where the
   powered entity cannot report the value in question itself (either
   because it can't report anything, or doesn't know the value in
   question, e.g. when metering is external).

   The second is where the powered entity can report, but the other
   entity is doing the reporting for some convenience.  We need to be
   aware of both even if the framework does not need to make the



Quittek, et al.         Expires January 12, 2012               [Page 28]


Internet-Draft     Requirements for Energy Management          July 2011


   distinction.

   There may be multiple other reporting entities, not just a single
   one.

   Do components of devices ever report, or do only devices do the
   reporting?  This seems like an important point.


13.  Informative References

   [RFC1628]  Case, J., "UPS Management Information Base", RFC 1628,
              May 1994.

   [RFC3433]  Bierman, A., Romascanu, D., and K. Norseth, "Entity Sensor
              Management Information Base", RFC 3433, December 2002.

   [RFC3621]  Berger, A. and D. Romascanu, "Power Ethernet MIB",
              RFC 3621, December 2003.

   [RFC3805]  Bergman, R., Lewis, H., and I. McDonald, "Printer MIB v2",
              RFC 3805, June 2004.

   [RFC4133]  Bierman, A. and K. McCloghrie, "Entity MIB (Version 3)",
              RFC 4133, August 2005.

   [RFC4268]  Chisholm, S. and D. Perkins, "Entity State MIB", RFC 4268,
              November 2005.

   [I-D.tychon-eman-applicability-statement]
              Tychon, E., Silver, L., and M. Chandramouli, "Energy
              Management (EMAN) Applicability Statement",
              draft-tychon-eman-applicability-statement-02 (work in
              progress), June 2011.

   [ACPI.R30b]
              Hewlett-Packard Corporation, Intel Corporation, Microsoft
              Corporation, Phoenix Corporation, and Toshiba Corporation,
              "Advanced Configuration and Power Interface Specification,
              Revision 3.0b", October 2006.

   [DMTF.DSP1027]
              Dasari (ed.), R., Davis (ed.), J., and J. Hilland (ed.),
              "Power State Management Profile", September 2008.

   [IEEE-ISTO]
              Printer Working Group, "PWG 5106.4 - PWG Power Management
              Model for Imaging Systems 1.0:", February 2011.



Quittek, et al.         Expires January 12, 2012               [Page 29]


Internet-Draft     Requirements for Energy Management          July 2011


   [IEC.62053-21]
              International Electrotechnical Commission, "Electricity
              metering equipment (a.c.) - Particular requirements - Part
              22: Static meters for active energy  (classes 1 and 2)",
              2003.

   [IEC.62053-22]
              International Electrotechnical Commission, "Electricity
              metering equipment (a.c.) - Particular requirements - Part
              22: Static meters for active energy  (classes 0,2 S and
              0,5 S)", 2003.

   [IEC.61850-7-4]
              International Electrotechnical Commission, "Communication
              networks and systems for power utility automation - Part
              7-4: Basic communication structure - Compatible logical
              node classes and data object classes", 2010.


Appendix A.  Existing Standards

   This section analyzes existing standards for energy consumption and
   power state monitoring.  It shows that there are already several
   standards that cover only some part of the requirements listed above,
   but even all together they do not cover all of the requirements for
   energy management.

A.1.  Existing IETF Standards

   There are already RFCs available that address a subset of the
   requirements.

A.1.1.  ENTITY MIB

   The ENTITY-MIB module defined in [RFC4133] was designed to model
   physical and logical entities of a managed system.  A physical entity
   is an identifiable physical component.  A logical entity can use one
   or more physical entities.  From an energy monitoring perspective of
   a managed system, the ENTITY-MIB modeling framework can be reused and
   whenever RFC 4133 [RFC4133] has been implemented.  The
   entPhysicalIndex from entPhysicalTable can be used to identify an
   entity/component.  However, there are use cases of energy monitoring,
   where the application of the ENTITY-MIB does not seem readily
   apparent and some of those entities could be beyond the original
   scope and intent of the ENTITY-MIB.

   Consider the case of remote devices attached to the network, and the
   network device could collect the energy measurement and report on



Quittek, et al.         Expires January 12, 2012               [Page 30]


Internet-Draft     Requirements for Energy Management          July 2011


   behalf of such attached devices.  Some of the remote devices such as
   PoE phones attached to a switch port have been considered in the
   Power-over-Ethernet MIB module [RFC3621].  However, there are many
   other devices such as a computer, which draw power from a wall outlet
   or building HVAC devices which seem to be beyond the original scope
   of the ENTITY-MIB.

   Yet another example, is smart-PDUs, which can report the energy
   consumption of the device attached to the power outlet of the PDU.
   In some cases, the device can be attached to multiple to power
   outlets.  Thus, the energy measured at multiple outlets need to be
   aggregated to determine the consumption of a single device.  From
   mapping perspective, between the PDU outlets and the device this is a
   many-to-one mapping.  It is not clear if such a many-to-one mapping
   is feasible within the ENTITY-MIB framework.

A.1.2.  ENTITY STATE MIB

   RFC 4268 [RFC4268] defines the ENTITY STATE MIB module.
   Implementations of this module provide information on entities
   including the standby status (hotStandby, coldStandby,
   providingService), the operational status (disabled, enabled,
   testing), the alarm status (underRepair, critical, major, minor,
   warning), and the usage status (idle, active, busy).  This
   information is already useful as input for policy decisions and for
   other network management tasks.  However, the number of states would
   cover only a small subset of the requirements for power state
   monitoring and it does not provide means for energy consumption
   monitoring.  For associating the information conveyed by the ENTITY
   STATE MIB to specific components of a device, the ENTITY STATE MIB
   module makes use of the means provided by the ENTITY MIB module
   [RFC4133].  Particularly, it uses the entPhysicalIndex for
   identifying entities.

   The standby status provided by the ENTITY STATE MIB module is related
   to power states required for energy management, but the number of
   states is too restricted for meeting all energy management
   requirements.  For energy management several more power states are
   required, such as different sleep and operational states as defined
   by the Advanced Configuration and Power Interface (ACPI) [ACPI.R30b]
   or the DMTF Power State Management Profile [DMTF.DSP1027].

A.1.3.  ENTITY SENSOR MIB

   RFC 3433 [RFC3433] defines the ENTITY SENSOR MIB module.
   Implementations of this module offer a generic way to provide data
   collected by a sensor.  A sensor could be an energy consumption meter
   delivering measured values in Watt.  This could be used for reporting



Quittek, et al.         Expires January 12, 2012               [Page 31]


Internet-Draft     Requirements for Energy Management          July 2011


   current power of an entity and its components.  Furthermore, the
   ENTITY SENSOR MIB can be used to retrieve the accuracy of the used
   power meter.

   Similar to the ENTITY STATE MIB module, the ENTITY SENSOR MIB module
   makes use of the means provided by the ENTITY MIB module [RFC4133]
   for relating provided information to components of a device.

   However, there is no unit available for reporting energy quantities,
   such as, for example, watt seconds or kilowatt hours, and the ENTITY
   SENSOR MIB module does not support reporting accuracy of measurements
   according to the IEC / ANSI accuracy classes, which are commonly in
   use for electric power and energy measurements.  The ENTITY SENSOR
   MIB modules only provides a coarse-grained method for indicating
   accuracy by stating the number of correct digits of fixed point
   values.

A.1.4.  UPS MIB

   RFC 1628 [RFC1628] defines the UPS MIB module.  Implementations of
   this module provide information on the current real power of entities
   attached to an uninterruptible power supply (UPS) device.  This
   application would require identifying which entity is attached to
   which port of the UPS device.

   UPS MIB provides information on the state of the UPS network.  The
   MIB module contains several variables that are used to identify the
   UPS entity (name, model,..), the battery state, to characterize the
   input load to the UPS, to characterize the output from the UPS, to
   indicate the various alarm events.  The measurements of power in UPS
   MIB are in Volts, Amperes and Watts.  The units of power measurement
   are RMS volts, RMS Amperes and are not based on Entity-Sensor MIB
   [RFC3433].

A.1.5.  POWER ETHERNET MIB

   Similar to the UPS MIB, implementations of the POWER ETHERNET MIB
   module defined in RFC3621 [RFC3621] provide information on the
   current energy consumption of the entities that receive Power over
   Ethernet (PoE).  This information can be retrieved at the power
   sourcing equipment.  Analogous to the UPS MIB, it is required to
   identify which entities are attached to which port of the power
   sourcing equipment.

   The POWER ETHERNET MIB does not report power and energy consumption
   on a per port basis, but can report aggregated values for groups of
   ports.  It does not use objects of the ENTITY MIB module for
   identifying entities, although this module existed already when the



Quittek, et al.         Expires January 12, 2012               [Page 32]


Internet-Draft     Requirements for Energy Management          July 2011


   POWER ETHERNET MIB modules was standardized.

A.1.6.  LLDP MED MIB

   The Link Layer Discovery Protocol (LLDP) defined in IEEE 802.1ab is a
   data link layer protocol used by network devices for advertising of
   their identities, capabilities, and interconnections on a LAN
   network.  The Media Endpoint Discovery (MED) (ANSI/TIA-1057) is an
   enhancement of LLDP known as LLDP-MED.  The LLDP-MED enhancements
   specifically address voice applications.  LLDP-MED covers 6 basic
   areas: capabilities discovery, LAN speed and duplex discovery,
   network policy discovery, location identification discovery,
   inventory discovery, and power discovery.

A.2.  Existing standards of other bodies

A.2.1.  DMTF

   The DMTF has defined a power state management profile [DMTF.DSP1027]
   that is targeted at computer systems.  It is based on the DMTF's
   Common Information Model (CIM) and rather an entity profile than an
   actual energy consumption monitoring standard.

   The power state management profile is used to describe and to manage
   the power state of computer systems.  This includes e.g. means to
   change the power state of an entity (e.g. to shutdown the entity)
   which is an aspect of but not sufficient for active energy
   management.

A.2.2.  OVDA

   ODVA is an association consisting of members from industrial
   automation companies.  ODVA supports standardization of network
   technologies based on the Common Industrial Protocol (CIP).  Within
   ODVA, there is a special interest group focused on energy and
   standardization and inter-operability of energy aware entities.

A.2.3.  IEEE-ISTO Printer WG

   The charter of the IEEE-ISTO Printer Working Group is for open
   standards that define printer related protocols, that printer
   manufacturers and related software vendors shall benefit from the
   interoperability provided by conformance to these standards.  One
   particular aspect the Printer WG is focused on is power monitoring
   and management of network printers and imaging systems PWG Power
   Management Model for Imaging Systems [IEEE-ISTO].  Clearly, these
   devices are within the scope of energy management since these devices
   consume power and are attached to the network.  In addition, there is



Quittek, et al.         Expires January 12, 2012               [Page 33]


Internet-Draft     Requirements for Energy Management          July 2011


   ample scope of power management since printers and imaging systems
   are not used that often.  IEEE-ISTO Printer working group has defined
   MIB modules for monitoring the power consumption and power state
   series that can be useful for power management of printers.  The
   energy management framework should also take into account the
   standards defined in the Printer working group.  In terms of other
   standards, IETF Printer MIB RFC3805 [RFC3805] has been standardized,
   however, this MIB module does not address power management of
   printers.


Authors' Addresses

   Juergen Quittek (editor)
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   DE

   Phone: +49 6221 4342-115
   Email: quittek@neclab.eu


   Rolf Winter
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   DE

   Phone: +49 6221 4342-121
   Email: Rolf.Winter@neclab.eu


   Thomas Dietz
   NEC Europe Ltd.
   NEC Laboratories Europe
   Network Research Division
   Kurfuersten-Anlage 36
   Heidelberg  69115
   DE

   Phone: +49 6221 4342-128
   Email: Thomas.Dietz@neclab.eu




Quittek, et al.         Expires January 12, 2012               [Page 34]


Internet-Draft     Requirements for Energy Management          July 2011


   Benoit Claise
   Cisco Systems, Inc.
   De Kleetlaan 6a b1
   Degem  1831
   BE

   Phone: +32 2 704 5622
   Email: bclaise@cisco.com


   Mouli Chandramouli
   Cisco Systems, Inc.
   Sarjapur Outer Ring Road
   Bangalore,
   IN

   Phone: +91 80 4426 3947
   Email: moulchan@cisco.com

































Quittek, et al.         Expires January 12, 2012               [Page 35]